Plan Review Notes
Plan Review Notes For Permit 02040434
Permit Number 02040434
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-10 00:00:00**************** UNSAT!*****************
  
 1} PLEASE PROVIDE LOAD CALCULATIONS PER
 ARTICLE 220-3(C)(1).
  
 2} SMOKE DETECTORS ARE REQUIRED PER
 NFPA-72.INSIDE AND OUT OF GARAGE
 ENCLOSURE.
  
 3} PLEASE INDICATE THE SIZE OF THE NEW
 JUNCTION BOX SHOWN ON THE OUTSIDE OF
 THE GARAGE AND THE SIZE & NUMBER OF
 CONDUCTORS IT CONTAINS.
  
 4} SHOW TYPE & SIZE OF CONDUIT TO THE
 PANEL FROM THE JUNCTION BOX,AND TYPE &
 SIZE OF WIRING IT CONTAINS,ALONG WITH
 THE NUMBER OF CONDUCTORS.
  
 5} PLEASE SUBMIT A DRAWING SHOWING THE
 NEW PANEL WITH IT'S AMPERAGE
 RATING,MEANS OF DISCONNECT,AND
 RISER,INCLUDING SIZE AND TYPE OF
 SERVICE CONDUCTORS AND ASSOCIATED
 FEEDERS.ALSO THE GROUNDING SYSTEM BEING
 USED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392