| 2003-04-04 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | |
| | PLAN REVIEW COMMENTS FROM 5-8-2, 10-5-2 |
| | 12/5/2 & 2-28-3 HAVE NOT BEEN ADDRESSED. |
| | |
| | 1) SHT A2, 1 AAUTOMATIC CLOTHES WASHER |
| | CONNECTION REQUIRED FOR EACH UNIT OR A |
| | CENTRAL FACILITY WITH 1 CONNECTION PER |
| | 20 UNITS REQUIRED PER TABLE 403.1. |
| | 2) SHT P1 PLUMBING NOTES #'2 2, 5, 6, 7, |
| | 8, 9, 10, & 11. CURRENT CODE IS FBC-2001 |
| | PLUMBING, NOT SFBC AS STATED IN NOTES. |
| | PLEASE CHANGE NOTES TO REFLECT PRESENT |
| | PLUMBING CODE. |
| | 3) SHT P2 1ST & 2ND FLOOR WATER RISER |
| | DIAGRAMS, AIR CHAMBERS ARE NOT APPROVED. |
| | WATER HAMMER ARRESTORS SHALL BE PROVIDED |
| | PER SECTION 604.9 AND LOCATED PER PDI-WH |
| | 201 AND MANUF. INSTALLATION INSTRUCTIONS |
| | 4) SHT P2 SANITARY RISER DIAGRAM, 2ND |
| | FLOOR BATHROOM GROUP SHALL NOT DRAIN IN- |
| | TO VENT OF 1ST FLOOR BATHROOM GROUP. 2ND |
| | FLOOR STACK SHALL BE TAKEN OFF BLDG |
| | DRAIN DOWNSTREAM OF 1ST FLOOR BATHROOM |
| | GROUP. |
| | 5) SHT P2 SANITARY RISER DIAGRAM, 3" |
| | VENT REQUIRED FOR MAIN STACK PER SEC. |
| | 903.1 |
| | 6) SEE ATTACHED SHEET CONCERNING FLORIDA |
| | STATUTE 553.80(2) (B). ADDITIONAL FEES |
| | SHALL BE IMPOSED AS THIS IS THE FIFTH |
| | TIME THESE COMMENTS HAVE BEEN ADDRESSED. |
| | |
| | |
| | REVIEW BY KEN STEVENS |