| 2002-12-03 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | |
| | 1) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2 |
| | SHT A2, 1 AUTOMATIC CLOTHES WASHER CON- |
| | NECTION REQUIRED FOR EACH UNIT OR A CEN- |
| | TRAL FACILITY WITH 1 CONNECTION PER 20 |
| | UNITS REQUIRED PER TABLE 403.1 |
| | 2) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2 |
| | SHT P1 PLUMBING NOTES, #'S 2, 5, 6, 7, 8 |
| | 9, 10, & 11. CURRENT CODE IS FBC-2001 |
| | PLUMBING, NOT SFBC AS STATED IN NOTES. |
| | PLEASE CHANGE NOTES TO REFLECT PRESENT |
| | PLUMBING CODE. |
| | 3) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2 |
| | SHT P1 PLUMBING NOTES #2 SHEET Z1 REFER- |
| | ENCED IN NOTE NOT SUBMITTED. PLEASE SUB- |
| | MIT ALL SHEETS FOR REVIEW. |
| | 4) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2 |
| | SHT P2 1ST & 2ND FLOOR WATER WATER RISER |
| | DIAGRAMS, AIR CHAMBERS ARE NOT APPROVED. |
| | WATER HAMMER ARRESTORS SHALL BE PROVIDED |
| | FOR WASH MACHINE, ICE MAKER, AND DISH |
| | WASHER IF PROVIDED. SEC 604.9 |
| | 5) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2 |
| | SHT P2 SANITARY RISER DIAGRAM, 2ND FLOOR |
| | BATHROOM GROUP SHALL NOT DRAIN INTO VENT |
| | OF 1ST FLOOR BATHROOM GROUP VENT. 2ND |
| | FLOOR STACK SHALL BE TAKEN OFF BLDG |
| | DRAIN DOWNSTREAM OF 1ST FLOOR BATHROOM |
| | GROUP. FLOOR PLAN DOES NOT SHOW KITCHEN |
| | ON SECOND FLOOR |
| | 6) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2 |
| | SHT P2 SANITARY RISER DIAGRAM, 3" VENT |
| | REQUIRED FOR MAIN STACK VENT PER SECTION |
| | 903.1 |
| | |