| 2003-04-14 00:00:00 | BUILDING DENIED |
| | |
| | 1) FBC 1606.1.7 WIND LOADS. THE PLANS |
| | SHALL STATE THE BASIC WIND SPEED, WIND |
| | IMPORTANCE FACTOR, WIND EXPOSURE |
| | CATEGORY, INTERNAL PRESSURE COEFFICENT, |
| | AND EXTERIOR COMPONENT AND CLADDING |
| | DESIGN WIND PRESSURES. THIS INFORMATION |
| | IS REQUIRED TO BE ON THE PLANS. |
| | |
| | 2) SHEETS A2 AND A4 CONTAIN REFERENCES |
| | TO THE WRONG CODE AND INCORRECT DESIGN |
| | CRITERIA. PLEASE CORRECT. |
| | |
| | 3) PROVIDE ENERGY CALCULATIONS. SEE FBC |
| | CHAPTER 13. |
| | |
| | 4) THE FASTENER SCHEDULE ON A4 REFERS TO |
| | SOUTH FLORIDA BUILDING CODE UNDER THE |
| | REMARKS COLUMN. PLEASE CORRECT TO FBC. |
| | |
| | 5)CORRECT NOTE #11 UNDER TYPICAL SECTION |
| | NOTES ON A4 AND THE DRYWALL FASTENER |
| | SPACING SPECIFIED ON DETAIL 1 AND DETAIL |
| | 5 ON A5 TO COMPLY WITH FBC TABLE 2306.1. |
| | |
| | 6) SPECIFY ON THE PLANS THAT ADEQUATE |
| | SUBSTRATE WILL BE PROVIDED AT THE |
| | WINDOWS FOR ATTACHMENT OF THE STORM |
| | PANELS. |
| | |
| | 7) PROVIDE (2) COPIES OF INSTALLATION |
| | SCHEDULE AND KEY PLAN FOR STORM PANELS. |
| | NOTE: THE PRODUCT APPROVALS THAT WERE |
| | SUBMITTED FOR STORM PANELS HAS EXPIRED. |
| | PLEASE SUBMIT CURRENT ONES. |
| | |
| | 8) STUCCO ON METAL LATH OVER SOLID BASE |
| | IS REQUIRED BY FBC 2504.2.1 AND ASTM C |
| | 926 TO BE 7/8" THICK. PLEASE REVISE ON |
| | WALL SECTIONS. |
| | |
| | 9) INDICATE THE ATTIC ACCESS ON THE |
| | PLANS. SEE FBC 2309.6. |
| | |
| | 10) FBC 1005.4 REQUIRES SLEEPING ROOMS |
| | TO HAVE AN EMERGENCY ESCAPE AND RESCUE |
| | OPENING. SEE CLEAR OPENING SIZE AND AREA |
| | REQUIREMENTS. THE 1/2- 34SH WINDOWS |
| | SHOWN ON THE PLANS DO NOT COMPLY. |
| | |
| | 11) PROVIDE DETAILS OF THE INTERIOR AND |
| | EXTERIOR STAIRS. SPECIFY THE RISER |
| | HEIGHTS AND TREAD DEPTHS. INDICATE THE |
| | FOUNDATION THAT SUPPORTS THE EXTERIOR |
| | STAIRS. |
| | |
| | 12) PROVIDE A SIGNED AND SEALED SURVEY |
| | INDICATING THE LOCATION OF THE STRUCTURE |
| | ON THE PROPERTY AND THE DISTANCE TO THE |
| | PROPERTY LINES. THIS IS REQUIRED TO |
| | DETERMINE THE PERCENT OF WALL AREA THAT |
| | IS ALLOWED AS OPENINGS. |
| | |
| | 13)PROVIDE EXTERIOR ELEVATIONS. INDICATE |
| | THE HEIGHT ABOVE GRADE TO FLOORS, |
| | CEILINGS, ETC. INDICATE THE MEAN ROOF |
| | HEIGHT AND ROOF PITCH. |
| | |
| | 14) SPECIFY THE POSITIVE AND NEGATIVE |
| | DESIGN WINDLOAD PRESSURES ON THE PLANS |
| | FOR ALL EXTERIOR OPENINGS. |
| | |
| | 15) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - EXTERIOR WOOD DOOR |
| | - EXTERIOR ALUMINUM DOOR |
| | THESE ARE THE EXTERIOR DOORS THAT ARE |
| | SPECIFIED ON THE PLANS IN THE DOOR |
| | SCHEDULE ON ON A2. IF YOU ARE NOT USING |
| | THESE DOORS, CHANGE THE SCHEDULE TO |
| | INDICATE THE DOORS THAT WILL BE USED. |
| | |
| | 16) THE DOOR SCHEDULE INDICATES THAT TWO |
| | EXTERIOR DOORS ARE HOLLOW CORE WOOD. |
| | THIS IS NOT ALLOWED BY FBC CHAPTER 13. |
| | (ENERGY EFFICIENCY) |
| | |
| | 17) THE COMMENTS NOTED IN PREVIOUS |
| | REVIEWS HAVE NOT BEEN ADDRESSED. FL |
| | STATUTE 553.80 (2) (B) REQUIRES A FEE OF |
| | FOUR TIMES THE PLAN REVIEW PORTION OF |
| | THE PERMIT FEE TO BE IMPOSED FOR EACH |
| | TIME AFTER THE THIRD REVIEW IN WHICH THE |
| | SAME ITEM HAS NOT BEEN CORRECTED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |