| 2003-02-20 00:00:00 | BUILDING DENIED |
| | THIS IS THE FOURTH STRUCTURAL REVIEW. |
| | |
| | 1) THE ENTIRE STRUCTURE SHALL BE MADE TO |
| | CONFORM THE REQUIREMENTS FOR A NEW |
| | STRUCTURE PER FBC 3401.7.2.6 AND THE |
| | CONSTRUCTION BOARD OF ADJUSTMENT AND |
| | APPEALS. |
| | |
| | 2) A SUCCESSOR PROFESSIONAL ENGINEER |
| | MUST USE HIS OWN TITLE BLOCK, SEAL AND |
| | SIGNATURE AND MUST REMOVE THE TITLE |
| | BLOCK, SEAL AND SIGNATURE OF THE |
| | ORIGINAL PROFESSIONAL ENGINEER BEFORE |
| | REUSING ANY SEALED CONTRACT DOCUMENTS. |
| | SEE FAC 61G15-27 FOR REQUIREMENTS. |
| | |
| | 3) FBC 1606.1.7WIND LOAD.THE PLANS |
| | SHALL STATE THE BASIC WIND SPEED, WIND |
| | IMPORTANCE FACTOR, WIND EXPOSURE |
| | CATEGORY, INTERNAL PRESSURE COEFFICIENT, |
| | AND EXTERIOR COMPONENT AND CLADDING |
| | DESIGN WIND PRESSURES. |
| | |
| | 4) SHEETS A2 AND A4 REFERENCE THE WRONG |
| | CODE AND DESIGN CRITERIA. PLEASE |
| | CORRECT. |
| | |
| | 5) PROVIDE ENERGY CALCULATIONS. SEE FBC |
| | CHAPTER 13. |
| | |
| | 6) THE FASTENER SCHEDULE ON A4 CONTAINS |
| | INCORRECT INFORMATION. REFER TO FBC |
| | TABLE 2306.1 AND CORRECT. |
| | |
| | 7) PLEASE CORRECT NOTE 11 ON A4 AND DRY- |
| | WALL FASTENER SPACING NOTE ON A5 TO |
| | COMPLY WITH FBC TABLE 2306.1. |
| | |
| | 8) SPECIFY ON THE PLANS ADEQUATE |
| | SUBSTRATE AT WINDOWS FOR THE ATTACHMENT |
| | OF STORM PANELS. |
| | |
| | 9) PROVIDE KEY PLANS AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. |
| | |
| | 10) STUCCO ON METAL LATH IS REQUIRED TO |
| | BE 7/8" THICK PER FBC 2504.2.1 AND ASTM |
| | C 926. PLEASE REVISE ON WALL SECTIONS. |
| | |
| | 11) INDICATE THE ATTIC ACCESS ON THE |
| | PLANS. SEE FBC 2309.6 |
| | |
| | 12) FBC 1005.4 REQUIRES SLEEPING ROOMS |
| | TO HAVE AN EMERGENCY ESCAPE AND RESCUE |
| | OPENING. SEE CLEAR OPENING SIZE AND AREA |
| | REQUIREMENTS. |
| | |
| | 13) PROVIDE DETAILS OF INTERIOR AND |
| | EXTERIOR STAIRS. SPECIFY THE RISER |
| | HEIGHT AND TREAD DEPTH. INDICATE THE |
| | FOUNDATION THAT SUPPORTS EXTERIOR STAIRS |
| | |
| | 14) PROVIDE A SIGNED AND SEALED SURVEY |
| | INDICATING THE LOCATION OF THE STRUCTURE |
| | ON THE PROPERTY AND THE DISTANCE TO THE |
| | PROPERTY LINES, IN ORDER TO DETERMINE |
| | COMPLIANCE WITH FBC TABLE 600. |
| | |
| | 15) PROVIDE EXTERIOR ELEVATIONS. |
| | INDICATE HEIGHTS ABOVE GRADE TO FLOORS, |
| | CEILINGS, ETC. INDICATE MEAN ROOF HEIGHT |
| | AND ROOF PITCH. |
| | |
| | 16) SPECIFY THE POSITIVE AND NEGATIVE |
| | DESIGN WINDLOAD PRESSURES ON THE PLANS |
| | FOR ALL EXTERIOR OPENINGS. |
| | |
| | 17) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - EXTERIOR WOOD DOOR |
| | - EXTERIOR ALUMNIUM DOOR |
| | THESE DOORS ARE SPECIFIED IN THE DOOR |
| | SCHEDULE ON A2. |
| | |
| | 18) THE DOOR SCHEDULE INDICATES THAT |
| | TWO EXTERIOR DOORS ARE HOLLOW CORE WOOD. |
| | THIS IS NOT ALLOWED BY FBC CHAPTER 13. |
| | (FL ENERGY CODE) |
| | |
| | 19) THE STRUCTURE IS REQUIRED TO BE |
| | RETURNED TO A SINGLE FAMILY DWELLING BY |
| | THE ZONING DEPARTMENT. PLEASE REVISE THE |
| | DRAWINGS TO REFLECT THIS. REMOVE THE |
| | SECOND FLOOR KITCHEN AND CHANGE TITLE |
| | BLOCK. |
| | |
| | MOST OF THESE COMMENTS WERE MADE IN THE |
| | THREE PREVIOUS REVIEWS AND HAVE NOT BEEN |
| | ADDRESSED. THE SAME PLANS HAVE BEEN |
| | SUBMITTED WITH NO REVISIONS BEING MADE. |
| | FLORIDA STATUTE 553.80(2)(B) REQUIRES A |
| | FEE OF FOUR TIMES THE PLAN REVIEW |
| | PORTION OF THE PERMIT FEE TO BE IMPOSED. |
| | SEE ATTACHMENT. |
| | IF YOU HAVE ANY QUESTIONS CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |