| 2002-05-08 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING. |
| | |
| | 1) SHT A2, 1 AUTOMATIC CLOTHES WASHER |
| | CONNECTION REQUIRED FOR EACH UNIT OR A |
| | CENTRAL FACILITY WITH I CONNECTION PER |
| | 20 UNITS REQUIRED PER TABLE 403.1 |
| | 2) SHT P1, WATER HEATER DETAIL, SHUT OFF |
| | VALVE REQUIRED FOR WATER HEATER. EMERGEN |
| | CY DRAIN PAN REQUIRED FOR ALL HEATERS |
| | ABOVE FIRST FLOOR. 3/4" PAN DRAIN LINE |
| | REQUIRED FOR PAN TERMINATING 6" ABOVE |
| | GRADE. |
| | 3) SHT P1 PLUMBING NOTES, #'S 2,5,6,7,8, |
| | 9,10, & 11. CURRENT CODE IS FBC-2001 |
| | PLUMBING, NOT SFBC AS STATED IN NOTES. |
| | PLEASE CHANGE NOTES TO REFLECT PRESENT |
| | PLUMBING CODE. |
| | 4) SHT P1 PLUMBING NOTES, NOTE #2 SHEET |
| | Z1 REFERENCED IN NOTE NOT SUBMITTED. |
| | PLEASE SUBMIT ALL SHEETS FOR REVIEW. |
| | 5) SHT P2 1ST & 2ND FLOOR WATER RISER |
| | DIAGRAMS, AIR CHAMBERS ARE NOT APPROVED. |
| | WATER HAMMER ARRESTORS SHALL BE PROVIDED |
| | FOR WASH MACHINE, ICE MAKER, & DISHWASH- |
| | ER IF PROVIDED. LOCATE W.H.A. NEAR FIX- |
| | TURE IN AN "EFFECTIVE RANGE" NOT AT TOP |
| | OF DROP. |
| | 6) SHT P2 SANITARY RISER DIAGRAM, 2ND |
| | FLOOR BATHROOM GROUP SHALL NOT DRAIN IN- |
| | TO VENT OF 1ST FLOOR BATHROOM GROUP VENT |
| | 2ND FLOOR STACK SHALL BE TAKEN OFF BLDG |
| | DRAIN DOWNSTREAM OF 1ST FLOOR BATHROOM |
| | GROUP. |
| | 7) SHT P2 SANITARY RISER DIAGRAM, 3" |
| | VENT REQUIRED FOR MAIN STACK VENT PER |
| | SEC 903.1 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |