| 2002-05-13 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | DUE TO THE CHANGE FROM A SINGLE FAMILY |
| | DWELLING TO A DUPLEX ADDITION IMPACT |
| | FEES MAY BE DUE TO PALM BEACH COUNTY. |
| | |
| | 2) PROVIDE ENERGY CALCULATIONS AND |
| | EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| | AS REQUIRED BY CHAPTER 13 OF THE FLORIDA |
| | BUILDING CODE, THE FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILDING |
| | CONSTRUCTION. |
| | |
| | 3) INDICATE DESIGN INFORMATION ON PLANS. |
| | 2001 FLORIDA BUILDING CODE AND ASCE7-98 |
| | NOT SFBC OR ASCE7-93. SHEETS A2 AND A4 |
| | REFERENCE THE WRONG CODE AND DESIGN |
| | CRITERIA. |
| | |
| | 4) FASTENING SCHEDULE ON A4 CONTAINS |
| | INCORRECT INFORMATION. PLEASE REFER TO |
| | TABLE 2306.1 IN THE 2001 FBC AND MAKE |
| | CORRECTIONS. |
| | |
| | 5) PLEASE CORRECT NOTE 11 ON A4 AND |
| | DRYWALL FASTENER SPACING NOTE ON A5 TO |
| | COMPLY WITH 2001FBC TABLE 2306.1 OR AS |
| | SPECIFIED BY MANUFACTURER. |
| | |
| | 6) INDICATE ON THE PLANS THAT ADEQUATE |
| | SUBSTRATE IS TO BE PROVIDED FOR THE |
| | ATTACHMENT OF STORM PANELS. |
| | |
| | 7) PROVIDE (2) COPIES OF AN INSTALLATION |
| | SCHEDULE AND KEY PLAN FOR HURRICANE |
| | PANELS. |
| | |
| | 8) STUCCO ON LATHE AS INDICATED ON WALL |
| | SECTIONS ON A5 IS REQUIRED TO BE 7/8" |
| | THICK PER FBC 2504.2.1 AND ASTM C 926. |
| | |
| | 9) A CONTINOUS LOAD PATH FROM THE ROOF |
| | TO THE FOUNDATION IS REQUIRED TO |
| | TRANSFER LOADS. NO CONNECTORS ARE SHOWN |
| | ON A5 BETWEEN THE FLOOR SILL AND STUDS |
| | OR BETWEEN 1ST AND 2ND FLOORS. PLEASE |
| | CORRECT. |
| | |
| | 10) FIREBLOCKING IS REQUIRED BETWEEN THE |
| | FLOOR AND WALL ASSEMBLIES AT THE 1ST AND |
| | 2ND FLOORS PER FBC 2305.1. PLEASE |
| | INDICATE ON PLANS. |
| | |
| | 11) INDICATE ATTIC ACCESS ON PLANS. |
| | FBC 2309.6 |
| | |
| | 12) EMERGENCY ESCAPE AND RESCUE OPENINGS |
| | ARE REQUIRED AT SLEEPING ROOMS PER FBC |
| | 1005.4. THE 1/2- 34SH WINDOWS INDICATED |
| | DO NOT PROVIDE THE REQUIRED NET CLEAR |
| | OPENING. PLEASE CORRECT. |
| | |
| | 13) A ONE HOUR TENANT SEPARATION IS |
| | REQUIRED BETWEEN UNITS PER FBC 704.2.2.3 |
| | AND 704.3.1. |
| | |
| | 14) INDICATE HOW THE REQUIRED MEANS OF |
| | EGRESS FROM THE SECOND FLOOR UNIT WILL |
| | BE PROVIDED. EXIT STAIRWAYS SHALL COMPLY |
| | WITH FBC 1006. PROVIDE STAIR DETAILS. |
| | |
| | 15) PROVIDE COPIES OF SURVEY INDICATING |
| | DISTANCES TO PROPERTY LINES IN ORDER TO |
| | DETERMINE COMPLIANCE WITH TABLE 600 FOR |
| | PERCENT OF WALL OPENINGS ALLOWED. |
| | |
| | 16) PROVIDE ELEVATIONS. INDICATE FLOOR, |
| | CEILING,ETC. HEIGHTS. INDICATE MEAN ROOF |
| | HEIGHT AND ROOF PITCH. |
| | |
| | 17) INDICATE THE POSITIVE AND NEGATIVE |
| | PRESSURES FOR ALL EXTERIOR DOOR AND |
| | WINDOW OPENINGS ON THE PLANS. |
| | |
| | 18) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - EXTERIOR WOOD DOOR |
| | - EXTERIOR ALUMINUM DOOR |
| | THE PRODUCT APPROVAL THAT WAS SUBMITTED |
| | WAS FOR EXTERIOR STEEL DOOR, WHICH IS |
| | NOT LISTED IN THE DOOR SCHEDULE ON A2. |
| | |
| | 19) THE DOOR SCHEDULE INDICATES THE |
| | EXTERIOR WOOD DOOR WITH A HOLLOW CORE. |
| | THIS IS NOT ALLOWED BY THE FLORIDA |
| | ENERGY CODE (FBC CHAPTER 13). |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |