Plan Review Notes
Plan Review Notes For Permit 02040248
Permit Number 02040248
Review Stop M
Sequence Number 1
Notes
Date Text
2002-04-08 00:00:002001 FLORIDA BUILDING CODE, MECHANICAL
 NFPA 96
  
 1.PROVIDE MANUFACTURER SUBMITTAL DATA
 & INSTALLATION INSTRUCTIONS FOR THE
 2 HR FIRE BLANKET.
  
 2.SHOW COMPLIANCE WITH 2001 FBC, MECH
 508.1.1.
  
 3.EXHAUST OUTLETS SHALL BE LOCATED NOT
 LESS THAN 10 FT FROM PARTS OF THE
 SAME OR CONTIGUOUS BUILDINGS,
 ADJACENT PROPERTY LINES & AIR INTAKE
  
 4.ADDITIONAL PERMIT REQUIRED FOR FIRE
 SUPRESSION.
  
 5.PROVIDE SUBMITTAL FOR THE DISHWASHER
 HOOD.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.