| Plan Review Notes For Permit 02040245 |
| Permit Number |
02040245 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-06-07 00:00:00 | PROVISO | | | ~~~~~~~ | | | 1} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG.(ON PANEL SCHED.) | | | | | | 2} THE #6 EQUIPMENT GROUND SHOWN BETWEEN | | | THE METER AND THE FIRST MEANS OF | | | DISCONNECT WOULD CAUSE A PARALLEL PATH | | | TO GROUND WITH THE GROUNDED CONDUCTOR | | | (NEUTRAL).DO NOT INSTALL AND REMOVE | | | FROM AS BUILTS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|