Plan Review Notes For Permit 02040245
Permit Number 02040245
Review Stop E
Sequence Number 2
Notes
Date Text
2002-06-07 00:00:00PROVISO
 ~~~~~~~
 1} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.(ON PANEL SCHED.)
  
 2} THE #6 EQUIPMENT GROUND SHOWN BETWEEN
 THE METER AND THE FIRST MEANS OF
 DISCONNECT WOULD CAUSE A PARALLEL PATH
 TO GROUND WITH THE GROUNDED CONDUCTOR
 (NEUTRAL).DO NOT INSTALL AND REMOVE
 FROM AS BUILTS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392