Plan Review Notes
Plan Review Notes For Permit 02040245
Permit Number 02040245
Review Stop R
Sequence Number 1
Notes
Date Text
2002-04-23 00:00:00*************BUILDING UNSAT*************
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE SOIL TEST PER SEC. 1804.2.2
 OF CITY AMENDMENTS TO THE 2001 FBC.
  
 3) PLEASE SPECIFY THE AMOUNT OF EMBED
 REQUIRED FOR THE 5/8" DIA. BOLTS AT THE
 C11 STEEL COLUMN BASES. SEE SCHEDULE ON
 A2.
  
 4) SAFETY GLAZING IS REQUIRED WITHIN 3'
 OF TUB/SHOWER ENCLOSURES PER 2001 FBC
 SECTION 2405.2.1(2). PLEASE INDICATE ON
 PLANS THAT THE BUTT GLASS AT HER BATH
 AND THE 2040 SH WINDOW IN HIS BATH WILL
 BE TEMPERED.
  
 5)THE ENGINEER WHOSE TITLE BLOCK APPEARS
 ON SHEETS A2,A3,A4,A5,A6 AND A7 IS
 REQUIRED TO SIGN, SEAL AND DATE THESE
 SHEETS.
  
 6) PROVIDE EMERGENCY EGRESS WINDOW IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGHT OF 24INCHES,NET CLEAR
 OPENING WIDTH OF 20 INCHES AND NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT
 SHALL NOT BE MORE THAN 44 INCHES ABOVE
 THE FLOOR. 2001 FBC 1005.4
 PLEASE NOTE THAT THE 2650 CASEMENT
 WINDOWS IN BEDROOMS #2 AND #3 DO NOT
 COMPLY. THE LIBRARY WHICH COULD BE USED
 AS A SLEEPING ROOM MUST HAVE EGRESS
 WINDOWS OR IT MUST BE PERMANENTLY NOTED
 ON THE PLANS THAT THIS ROOM IS NOT TO BE
 USED FOR SLEEPING PURPOSES.
  
 8) PLEASE NOTE THE SIZE OF THE T-NAILS
 USED TO FASTEN THE 1X4 P.T. WINDOW AND
 SLIDING GLASS DOOR BUCKS.
  
 9) PLEASE CLARIFY THE B AND D MARKS ON
 A3 WHICH APPEAR TO BE POSITIVE AND
 NEGATIVE PRESSURES. HOWEVER,THEY DO NOT
 COINCIDE WITH THE WIND PRESSURES
 ASSIGNED TO B AND D ON A5.
  
 10)PROVIDE MANUFACTURER'S SPECIFICATIONS
 AND UL LISTING FOR BBQ ON THE COVERED
 PORCH AND THE PREFAB FIREPLACE AND
 FLUE PIPE.
  
 11) DETAILS 21 & 22 ON A8 FOR THE STEEL
 COLUMN BASES DO NOT CORRESPOND WITH THE
 STEEL COLUMNS LISTED IN THE COLUMN
 SCHEDULE ON A2. PLEASE REVISE.
  
 12) PROVIDE ENGINEERED CUT SHEETS FROM
 THE TRUSS MANUFACTURER FOR THE CHIMNEY
 SHOWN ON DETAIL 1 SHEET A9 PRIOR TO
 INSTALLING. INDICATE APPROPRIATE
 CONNECTORS TO RESIST WINDLOADS.
  
 13) THE TOTAL THICKNESS OF THE STUCCO ON
 THE EXTERIOR OF THE CHIMNEY IS REQUIRED
 TO BE 7/8" THICK PER 2001 FBC SECTION
 2504.2.1 AND ASTM C 926. PLEASE CORRECT
 DETAIL 1 ON A9.
  
 14) THE CONNECTORS SPECIFIED FOR K & L
 IN THE TRUSS ANCHOR SCHEDULE ON A7 AS
 UCS SHOULD BE USC. PLEASE CORRECT.
  
 15) ITEM (I) IN THE WIND LOAD CHART ON
 A7 STATES THAT ALL DOORS, WINDOWS AND
 SKYLIGHTS ARE IMPACT RESISTANT. HOWEVER,
 SOME OF THE PRODUCT APPROVALS DO NOT
 INDICATE IMPACT RESISTANT GLAZING.
 PLEASE CORRECT.
  
 16) ITEM (C) IN THE CHART ON A7 APPEARS
 TO HAVE A TYPO AT MPH. PLEASE CORRECT.
  
 17) PROVIDE (2) COPIES OF KEY PLANS AND
 INSTALLATION SCHEDULES FOR THE STORM
 PANELS. INDICATETHE SPECIFIC ANCHORS
 THAT WILL BE USED FOR STORM PANELS ON
 THE PRODUCT APPROVALS.
  
 18) THE SITE SPECIFIC ENGINEERING FOR
 THE FIXED GLASS, BUTT GLASS AND
 STRUCTURAL MULLIONS ARE REQUIRED TO BE
 REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD FOR THE STRUCTURE. USE THE CITY
 OF WPB PRODUCT APPROVAL FORM TWO COPIES
 FOR EACH ITEM. FORM IS REQUIRED TO BE
 SIGNED AND SEALED BY BOTH THE ENGINEER
 CERTIFYING THE PRODUCT AND THE DESIGNER
 OF RECORD. A LETTER OF APPROVAL SIGNED,
 SEALED AND DATED BY THE DESIGNER OF
 RECORD IS ALSO ACCEPTABLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202