| 2002-04-09 00:00:00 | ****************** UNSAT! ************** | | | | | | PLEASE NOTE THE FOLLOWING AND RESUBMIT | | | FOR REVIEW ; | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE REDRAW THE SERVICE GROUNDING | | | SYSTEM TO COMPLY WITH 250-50. | | | | | | 3} THE GFI IN "HIS" BATH IS NOT | | | SHOWN.PLEASE INCLUDE PER 210-52(D) & | | | 210-11(3). | | | | | | 4} NOTE;BEDROOMS TO COMPLY WITH 210-12. | | | | | | 5} PLEASE RECHECK THE LOAD CALCULATIONS | | | AND MAKE ANY CHANGES NECESSARY. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|