2002-04-29 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-ENGINEER TO SEE SECTION 1606.1.7 OF
 FBC 2001 FOR MINIMUM INFORMATION
 REQUIRED ON PLANS.
 3-ENGINEER TO HAVE ALL HIS PROFESSIONAL
 INFORMATION IN ALL DRAWINGS AS REQ'D
 BY CHAPTER 471 FLORIDA STATUTES.
 -ALSO, ALL DRAWINGS TO HAVE ORIGINAL
 SIGNATURE AND BE DATED THE DATE OF
 SEALING AS REQUIRED BY CHAPTER 471 F.S
 4-ENGINEER SPECIFY THE DESIGN PRESSURES
 CALCULATED AT ALL EXTERIOR OPENINGS.
 SEC. 1606.2.2.1 FBC 2001.
 5-REVISE ENERGY CALCULATIONS:
 PREDOMINANT EAVE OVERHANG IS INCORRECT
 SEE DRAWINGS.
 -ALSO, OWNER/AGENT TO SIGN AND DATE
 BOTTOM OF FORM.
 -ALSO, CLIMATE ZONE CHECKED ON TOP OF
 FORM IS INCORRECT. REVISE.
 6-ENGINEER TO SPECIFY HOW IS NEW WALL &
 FOOTING GOING TO BE ATTACHED TO
 EXISTING WALL AND FOUNDATION. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-ROOF FRAMING PLAN: ESPECIFY UPLIFT
 LOADS CALCULATED AND CORRESPONDING
 ANCHOR. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 8-PROVIDE PRODUCT APPROVAL FOR:
 A)SINGLE HUNG WINDOWS WITH LEGIBLE DWGS
 B)EXTERIOR SWING DOOR.
  
 9-ENGINEER TO PROVIDE DOOR AND WINDOW
 STRUCTURAL BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001 AND PRODUCT
 APPROVAL FOR DOORS AND WINDOWS USED
 IN THIS PROJECT.
 10-OWES $105.14 FOR UPDATED PROJECT
 VALUATION AND RADON FEES.