| 2002-04-29 00:00:00 | CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-ENGINEER TO SEE SECTION 1606.1.7 OF |
| | FBC 2001 FOR MINIMUM INFORMATION |
| | REQUIRED ON PLANS. |
| | 3-ENGINEER TO HAVE ALL HIS PROFESSIONAL |
| | INFORMATION IN ALL DRAWINGS AS REQ'D |
| | BY CHAPTER 471 FLORIDA STATUTES. |
| | -ALSO, ALL DRAWINGS TO HAVE ORIGINAL |
| | SIGNATURE AND BE DATED THE DATE OF |
| | SEALING AS REQUIRED BY CHAPTER 471 F.S |
| | 4-ENGINEER SPECIFY THE DESIGN PRESSURES |
| | CALCULATED AT ALL EXTERIOR OPENINGS. |
| | SEC. 1606.2.2.1 FBC 2001. |
| | 5-REVISE ENERGY CALCULATIONS: |
| | PREDOMINANT EAVE OVERHANG IS INCORRECT |
| | SEE DRAWINGS. |
| | -ALSO, OWNER/AGENT TO SIGN AND DATE |
| | BOTTOM OF FORM. |
| | -ALSO, CLIMATE ZONE CHECKED ON TOP OF |
| | FORM IS INCORRECT. REVISE. |
| | 6-ENGINEER TO SPECIFY HOW IS NEW WALL & |
| | FOOTING GOING TO BE ATTACHED TO |
| | EXISTING WALL AND FOUNDATION. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 7-ROOF FRAMING PLAN: ESPECIFY UPLIFT |
| | LOADS CALCULATED AND CORRESPONDING |
| | ANCHOR. SEC. 104.2.1.2 CITY AMENDMENTS |
| | TO FBC 2001. |
| | 8-PROVIDE PRODUCT APPROVAL FOR: |
| | A)SINGLE HUNG WINDOWS WITH LEGIBLE DWGS |
| | B)EXTERIOR SWING DOOR. |
| | |
| | 9-ENGINEER TO PROVIDE DOOR AND WINDOW |
| | STRUCTURAL BUCK DETAIL. SEE SECTION |
| | 1707.4.4.2 FBC 2001 AND PRODUCT |
| | APPROVAL FOR DOORS AND WINDOWS USED |
| | IN THIS PROJECT. |
| | 10-OWES $105.14 FOR UPDATED PROJECT |