| Plan Review Notes For Permit 02040154 |
| Permit Number |
02040154 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-02-19 00:00:00 | ************* UNSAT ******************* | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM, NOW | | | A NEW 300A MAIN DISC HAS BEEN ADDED? | | | PLEASE SEE 310-15FOR SIZING OF | | | CONDUCTORS, SHOWN AS 2/0'S WHICH ARE | | | ONLY RATED FOR 200A'S. | | | | | | 2)NOTE: PLEASE SEE 250-66 FOR SIZING OF | | | GROUNDING ELECTRODE PER SEC. | | | | | | 3)NOTE: PLEASE CLARIFY SIZE OF METERCAN | | | IF SERVICE IS GOING TO BE 400A AS SHOWN. | | | | | | | | | 4)NOTE: PLEASE SHOW LOCATIONS OF MAIN | | | DISC'S. MAINS ARE TO BE GROUPED PER | | | 230-72.SHOW ON PLAN. | | | | | | 5)NOTE: RISER ON A-11 SHOWS AN EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN DISC | | | AND METER. PLEASE SEE 250-24, AND REMOVE | | | , ONLY AFTER THE FIRST MEANS OF DISC | | | IS AN EQUIPMENT GROUND INSTALLED. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|