Plan Review Notes
Plan Review Notes For Permit 02040154
Permit Number 02040154
Review Stop E
Sequence Number 2
Notes
Date Text
2002-06-11 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE NOW A RISER DIAGRAM
 IS BEING SUBMITTED INCLUDING A PANEL
 FOR GARAGE.
 PLEASE NOTE PER 230-72 GROUPING OF MAINS
 AT MAIN SERVICE. MAIN DISC REQ`D AT
 METER LOCATION TO FEED GARAGE PANEL.
 PLEASE ALSO NOTE NO CONDUIT/WIRE SIZES
 AND GROUNDING SHOWN TO OR AT GARAGE
 PANEL. GARAGE ALSO NEEDS A MAIN DISC IF
 PANEL HAS MORETHAN 6 SPACES.
 RECEPT IN GARAGE TO BE GFI 210-8
  
 2)NOTE: PLEASE NOTE THAT ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO GFI
 /GFI PROTECTED. PER 210-8-A-6. INCLUDING
 PENINSULAR.
  
 3)NOTE: PLEASE NOTE BATHROOM STILL
 MISSING EGRESS LIGHTING PER 210-70
 EXIST BATH.
  
 4)NOTE: PLEASE NOTE OUTLET SPACING IN
 EXISTING BEDROOM AND LIV RM WILL BE REQ`
 D TO BE BROUGHT UP TO CODE IF EXIST DOES
 NOT MEET 210-52. ??
  
 5)NOTE: PLEASE NOTE, JUST AS A NOTE,
 SEEMS KITCHEN COUNTER AT END MAY BE 12"
 OR MORE WHICH WOULD REQ` AN OUTLET.
 210-52-C-1
  
 PLEASE NOTE THAT MOST NOTES ARE FROM
 FIRST REVIEW. PLEASE SUBMIT THE ABOVE
 AND IF THERE ARE ANY QUESTIONS,PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 6)NOTE: PLEASE NOTE ON FIRST SET OF PLAN
 -S, A RECEPT WAS SHOWN WITHIN 5' OF POOL
 WHICH IS NOT ALLOWED, THAT WAS REMOVED,
 HOWEVER ONE IS REQ`D WITHIN 20`. PLEASE
 SEE 680-6(A).