| 2002-06-11 00:00:00 | **************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE NOTE NOW A RISER DIAGRAM |
| | IS BEING SUBMITTED INCLUDING A PANEL |
| | FOR GARAGE. |
| | PLEASE NOTE PER 230-72 GROUPING OF MAINS |
| | AT MAIN SERVICE. MAIN DISC REQ`D AT |
| | METER LOCATION TO FEED GARAGE PANEL. |
| | PLEASE ALSO NOTE NO CONDUIT/WIRE SIZES |
| | AND GROUNDING SHOWN TO OR AT GARAGE |
| | PANEL. GARAGE ALSO NEEDS A MAIN DISC IF |
| | PANEL HAS MORETHAN 6 SPACES. |
| | RECEPT IN GARAGE TO BE GFI 210-8 |
| | |
| | 2)NOTE: PLEASE NOTE THAT ALL OUTLETS |
| | SERVING KITCHEN COUNTERSPACE ARE TO GFI |
| | /GFI PROTECTED. PER 210-8-A-6. INCLUDING |
| | PENINSULAR. |
| | |
| | 3)NOTE: PLEASE NOTE BATHROOM STILL |
| | MISSING EGRESS LIGHTING PER 210-70 |
| | EXIST BATH. |
| | |
| | 4)NOTE: PLEASE NOTE OUTLET SPACING IN |
| | EXISTING BEDROOM AND LIV RM WILL BE REQ` |
| | D TO BE BROUGHT UP TO CODE IF EXIST DOES |
| | NOT MEET 210-52. ?? |
| | |
| | 5)NOTE: PLEASE NOTE, JUST AS A NOTE, |
| | SEEMS KITCHEN COUNTER AT END MAY BE 12" |
| | OR MORE WHICH WOULD REQ` AN OUTLET. |
| | 210-52-C-1 |
| | |
| | PLEASE NOTE THAT MOST NOTES ARE FROM |
| | FIRST REVIEW. PLEASE SUBMIT THE ABOVE |
| | AND IF THERE ARE ANY QUESTIONS,PLEASE |
| | CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |
| | |
| | 6)NOTE: PLEASE NOTE ON FIRST SET OF PLAN |
| | -S, A RECEPT WAS SHOWN WITHIN 5' OF POOL |
| | WHICH IS NOT ALLOWED, THAT WAS REMOVED, |
| | HOWEVER ONE IS REQ`D WITHIN 20`. PLEASE |
| | SEE 680-6(A). |