| 2002-04-12 00:00:00 | **************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE NOTE THAT UNLESS THE |
| | FEED FROM METER TO PANEL IS UNDERGROUND |
| | (SLAB). MORE THAN 8' OF UNPROTECTED |
| | CONDUCTORS IS NOT ALLOWED IN BLDG. |
| | PLEASE NOTE THAT A MAIN DISC WILL BE |
| | REQ`D WITH OCP. |
| | |
| | 2)NOTE: PLEASE NOTE THAT IF INSTALLING A |
| | NEW MAIN DISCONNECT THEN, PLEASE SUBMIT |
| | THE AIC RATING FOR NEW MAIN. 110-9 |
| | |
| | 3)NOTE: PLEASE CLARIFY OUTLETS SHOWN |
| | AROUND THE OUTSIDE OF HOUSE. NOT SHOWN |
| | ON ELECTRICAL DETAIL ON LEFT? PLEASE |
| | SHOW ALL AS GFI/GFI PROTECTED PER 210-8. |
| | |
| | |
| | 4)NOTE: PLEASE NOTE THAT OUTLETS SHOWN |
| | AROUND POOL ARE SHOWN CLOSER THAN THE |
| | 5' PERMITTED PER 680-6A. |
| | |
| | 5)NOTE: PLEASE NOTE THAT THERE BATHROOMS |
| | THAT DO NOT SHOW GFI OUTLETS REQ`D PER |
| | 210-52D PLEASE NOTE THAT 210-8 |
| | PLEASE CLARIFY IF EXISITNG? |
| | |
| | 6) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG. |
| | |
| | 7 )NOTE: PLEASE LIST THE REQ`D ARC |
| | FAULT PROECTED CIRCUITS ON PANEL |
| | SCHEDULE. PER 210-12 |
| | |
| | 8) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | INCLUDES KITCHEN ISLANDS. |
| | |
| | 9)NOTE: PLEASE NOTE CIRCUIT SHOWN FOR |
| | WALL OVEN IS SHOWN AT 4500W WITH #12? |
| | PLEASE CORRECT. |
| | |
| | 10)NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | MISSINGONE INMASTER BEDROOM. |
| | |
| | 11)NOTE: PLEASE CLARIFY CIRCUIT WATTAGE |
| | FOR COND UNIT. SHOWN W/2P-50 AND ONLY |
| | 1200WATTS. |
| | |
| | 12)NOTE: PLEASE NOTE THAT DISCONNECTING |
| | MEANS SHALL BE PROVIDED FOR ALL |
| | UNGROUNDED CONDUCTORS THAT SUPPLY OR |
| | PASS THROUGH A BLDG/STRUCTURE. |
| | PER 225-31. PLEASE ALSO NOTE GROUNDING |
| | PER 250-50/250-32 |
| | PLEASE NOTE THAT THERE IS NOTHING ON |
| | PANEL SCHEDULE ABOUT GARAGE, PLEASE |
| | CLARIFY. |
| | |
| | PLEASE SUBMIT THE ABOVEINFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |