2002-05-09 00:00:00BUILDING DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 4) STUCCO THICKNESS ON VERTICAL METAL
 LATHE IS REQUIRED TO BE 7/8" PER ASTM
 C 926 AND 2504.2.1 FBC. PLEASE CORRECT
 WALL SECTIONS B&C ON A10.
  
 5) A CLEARANCE OF 6" IS REQUIRED BETWEEN
 EXTERIOR WALL COVERINGS AND FINAL GRADE
 FOR INSPECTION FOR TERMITE INFESTION.
 1403.1.6 FBC PLEASE INDICATE ON WALL
 SECTIONS B&C ON A10.
  
 6) PROVIDE EMERGENCY EGRESS WINDOW IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGHT OF 24INCHES,NET CLEAR
 OPENING WIDTH OF 20 INCHES AND NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT
 SHALL NOT BE MORE THAN 44 INCHES ABOVE
 THE FLOOR. 1005.4 FBC & CITY AMENDMENTS
 THE 24SH WINDOWS IN BR #2 TYPICALLY DO
 NOT PROVIDE THE REQUIRED OPENING HEIGHT.
 THE EXISTING WINDOW IN BR #3 MUST COMPLY
 OR BE REPLACED WITH A WINDOW THAT DOES.
  
 7) INDICATE ATTIC ACCESS IN HOUSE AND
 DETACHED GARAGE TO COMPLY WITH 2309.6FBC
  
 8) INDICATE THE SIZE OF THE ATTIC VENTS
 ON A10 AND PROVIDE CALCULATIONS WHICH
 INDICATE THE TOTAL NET FREE VENTILATING
 AREA TO CEILING AREA AS REQUIRED BY
 2309.7 FBC.
  
 9) INDICATE ON THE PLANS THAT THE WELDED
 WIRE MESH LISTED IN THE FOUNDATION NOTES
 ON G1 SHALL BE SUPPORTED IN A MANNER
 THAT COMPLIES WITH 1909.3 FBC.
  
 10) THE ROOF SHEATHING NAILING DIAGRAM
 ON A7 SHOULD INDICATE 5'(INCLUDING OVER-
 HANG) AT THE GABLE END (ZONE 3). CITY
 AMENDMENTS 2306.1
  
 11) INDICATE THE POSITIVE AND NEGATIVE
 PRESSURES ON THE ELEVATIONS FOR ALL NEW
 WINDOW AND DOOR OPENINGS.
  
 12) THE REAR ELEVATION EXCEEDS TABLE 600
 FBC FOR THE PERCENTAGE OF OPENINGS
 ALLOWED. WALLS WITHIN 3'-10' OF THE
 PROPERTY LINE ARE ALLOWED TO HAVE 20 %
 OF THE WALL AREA AS OPENINGS, WHICH IS
 52 SQFT. IN THIS CASE. WITH 1 HOUR FIRE
 RATED GLASS BLOCK IN THE BATHROOM THE
 REMAINING WINDOW AREA IS 55.3 SQFT.
  
 13) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALCULATION FORM.
  
 14) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL MULLIONS
 - GLASS BLOCK
  
 15) SECTION 1707.4.4.2 OF FBC REQUIRES
 THAT TAPERED BUCKS EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME. WHERE BUCK THICKNESS IS LESS THAN
 1-1/2" THE WINDOW AND DOOR ASSEMBLIES
 ARE REQUIRED TO TO BE ANCHORED THROUGH
 THE BUCKS TO THE STRUCTURAL SUBSTRATE.
 PLEASE REVIEW THE BUCK DETAILS ON G2
 AND REVISE AS NECESSARY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202