2002-04-03 00:00:002001 FLORIDA BUILDING CODE, MECHANICAL
  
 1.INDICATE SIZE & LOCATION OF RETURN
 AIR GRILLE.
  
 2.BALANCED RETURN AIR - WHERE RETURN
 IS CENTERALLY LOCATED & TO AVOID
 PRESSURE DIFFERENTIALS ACROSS CLOSED
 DOORS, PROVIDE AIR DUCT PATHWAYS OR
 AIR TRANSFER FROM THE HIGH PRESSURE
 ZONES TO LOW ZONE.601.4
  
 3.BALANCING DAMPERS OR OTHER MEANS OF
 SUPPLY AIR ADJUSTMENT SHALL BE
 PROVIDED IN THE BRANCH DUCTS OR AT
 EACH INDIVIDUAL DUCT REGISTER,
 GRILLE OR DIFFUSER.603.15
  