| Plan Review Notes For Permit 02040109 |
| Permit Number |
02040109 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-03 00:00:00 | 2001 FLORIDA BUILDING CODE, MECHANICAL | | | | | | 1.INDICATE SIZE & LOCATION OF RETURN | | | AIR GRILLE. | | | | | | 2.BALANCED RETURN AIR - WHERE RETURN | | | IS CENTERALLY LOCATED & TO AVOID | | | PRESSURE DIFFERENTIALS ACROSS CLOSED | | | DOORS, PROVIDE AIR DUCT PATHWAYS OR | | | AIR TRANSFER FROM THE HIGH PRESSURE | | | ZONES TO LOW ZONE.601.4 | | | | | | 3.BALANCING DAMPERS OR OTHER MEANS OF | | | SUPPLY AIR ADJUSTMENT SHALL BE | | | PROVIDED IN THE BRANCH DUCTS OR AT | | | EACH INDIVIDUAL DUCT REGISTER, | | | GRILLE OR DIFFUSER.603.15 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|