Plan Review Notes
Plan Review Notes For Permit 02040100
Permit Number 02040100
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-25 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT PLANS STILL
 SHOW NEC ARTS FROM 96 NEC. PLEASE
 CORRELATE #`S WITH 99 NEC.
  
 2)NOTE: PLEASE NOTE MISPRINT FOR AIC
 RATING OF MAIN.22.00? INSTEAD OF 22,000.
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS PRE 210-12.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372