| Plan Review Notes For Permit 02040096 |
| Permit Number |
02040096 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-10 00:00:00 | ****************UNSAT!****************** | | | 1} PLEASE CLARIFY EQUIPMENT | | | GROUNDING METHOD BETWEEN FIRST MEANS | | | OF DISCONNECT AND PANELS. PLEASE SIZE | | | CONDUCTORS PER 250-122. | | | | | | 2}PLEASE NOTE MISSING OUTLET FOR | | | A/C EQUIPMENT. PER 210-63 AND/OR SECTION | | | 306 OF THE MECHANICAL CODE. | | | | | | 3}PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE. PER 210-12 | | | | | | 4}CODE ARTICLES IN THE ELECTRICAL NOTES | | | ARE INCORRECT. | | | | | | 5}PLEASE NOTE AIC @ 22.00? | | | | | | PLEASE MAKE CORRECTIONS AND RESUBMIT FOR | | | REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|