Plan Review Notes
Plan Review Notes For Permit 02040096
Permit Number 02040096
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-10 00:00:00****************UNSAT!******************
 1} PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 2}PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 3}PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 4}CODE ARTICLES IN THE ELECTRICAL NOTES
 ARE INCORRECT.
  
 5}PLEASE NOTE AIC @ 22.00?
  
 PLEASE MAKE CORRECTIONS AND RESUBMIT FOR
 REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392