Plan Review Notes
Plan Review Notes For Permit 02040094
Permit Number 02040094
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-10 00:00:00******************UNSAT!****************
  
 1)NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 2} PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 3} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 4} NOTE AIC@ 22.00?
  
 5} CODE ARTICLES LISTED IN THE
 ELECTRICAL NOTES AREINCORRECT.
  
 PLEASE MAKE NECESSARY CORRECTIONS AND
 RESUBMIT FOR REVIEW
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392