| Plan Review Notes For Permit 02040091 |
| Permit Number |
02040091 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-25 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT THE WRONG CODES | | | ARE REFERENCED. 96 NEC SHOWN AND WE ARE | | | UNDER THE 99 NEC. PLEASE CORRECT. | | | | | | 2)NOTE: PLEASE THAT THE AIC RATING IS | | | SHOWN AS 22.00 INSTEAD OF 22,000 AIC. | | | A MISPRINT. | | | | | | 3 )NOTE: PLEASE CLARIFY EQUIPMENT | | | GROUNDING METHOD BETWEEN FIRST MEANS | | | OF DISCONNECT AND PANELS. PLEASE SIZE | | | CONDUCTORS PER 250-122. | | | | | | 4))NOTE: PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS. | | | SCHEDULE. PER 210-12 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE AREANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|