2003-01-24 00:00:00**************** UNSAT ***************
  
 1)PLEASE SEE RISER DIAGRAM AND PLANS,
 THERE ARE MANY ITMES THAT DO NOT
 CORRELATE.
 SHOWS 250A SERVICE AND 225 DISC,225A
 PANEL W/ 250A BRKRS, 50A SUB PANEL W/
 68.75A LOAD W/ 75A OCP AND ONLY #6 WIRE
 ON RISER BUT SHOW #4 ON PANEL SCHEDULE.
  
 2)NOTE: MISSING EQUIPMENT GROUNDING
 CONDUCTORS BETWEEN MAIN AND PANELS,
 SIZE PER 250-122
  
 3)NOTE: PLEASE NOTE, PLANS CAME IN FOR
 AN ADDITION ON GARAGE AND NO ELECTRICAL
 SHOWN. PLEASE REVISE ON E-SHEET FOR
 LAYOUT OF ADD.
  
 PLEASE NOTE PLANS HAVE HAD THE SAME NOTE
 S ON PREVIOUS REVIEW. PLEASE ADDRESS
 COMMENTS.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED. MAINS
 PANELS, BRKRS ARE ALL TO BE RATED FOR
 THE AVAILABLE FAULT CURRENT. 110-9
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372