| Plan Review Notes For Permit 02040084 |
| Permit Number |
02040084 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-01-24 00:00:00 | **************** UNSAT *************** | | | | | | 1)PLEASE SEE RISER DIAGRAM AND PLANS, | | | THERE ARE MANY ITMES THAT DO NOT | | | CORRELATE. | | | SHOWS 250A SERVICE AND 225 DISC,225A | | | PANEL W/ 250A BRKRS, 50A SUB PANEL W/ | | | 68.75A LOAD W/ 75A OCP AND ONLY #6 WIRE | | | ON RISER BUT SHOW #4 ON PANEL SCHEDULE. | | | | | | 2)NOTE: MISSING EQUIPMENT GROUNDING | | | CONDUCTORS BETWEEN MAIN AND PANELS, | | | SIZE PER 250-122 | | | | | | 3)NOTE: PLEASE NOTE, PLANS CAME IN FOR | | | AN ADDITION ON GARAGE AND NO ELECTRICAL | | | SHOWN. PLEASE REVISE ON E-SHEET FOR | | | LAYOUT OF ADD. | | | | | | PLEASE NOTE PLANS HAVE HAD THE SAME NOTE | | | S ON PREVIOUS REVIEW. PLEASE ADDRESS | | | COMMENTS. | | | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. MAINS | | | PANELS, BRKRS ARE ALL TO BE RATED FOR | | | THE AVAILABLE FAULT CURRENT. 110-9 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|