| Plan Review Notes For Permit 02040084 |
| Permit Number |
02040084 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-07-16 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THE FOLLOWING DISCREPANCIES | | | ON PLANS,MAKE ANY NECESSARY CHANGES AND | | | RESUBMIT FOR REVIEW. | | | | | | 1} THE EQUIPMENT GROUND BETWEEN THE | | | METER AND THE MAIN DISCONNECT NEEDS TO | | | BE REMOVED. SEE NOTE #2 LAST REVIEW. | | | | | | 2} PLEASE NOTE THE SINGLE POLE 50 AMP | | | BREAKER SHOWN FEEDING PANEL "B",CIRCUIT | | | 38 IN PANEL "A". | | | | | | 3} PLEASE SHOW METER ON THE PLANS. | | | | | | 4} PLEASE NOTE CIRCUIT # 21 INDICATES A | | | SMALL APPLIANCE CIRCUIT AND LAUNDRY | | | CIRCUIT,THESE MUST BE SEPERATED PER | | | 210-11(C)(2). | | | | | | 5} THE LOAD CALCULATIONS FOR PANEL "B" | | | IS SHOWN AT 7.5 KW PER PHASE EQUALLING | | | 15KW,WHICH DIVIDED BY 240 VOLTS=62.5 | | | AMPS,EXCEEDING THE PANEL RATING,AND THE | | | OCP FEEDING SAME. | | | | | | 6} PLEASE NOTE THE SWITCH LOCATED ON THE | | | ROOF FOR THE STAIRWELL SHOULD BE A | | | 3-WAY. | | | | | | 7} NOTE CIRCUIT # 41 FOR BR#1 IS SHOWN | | | AS A GFI,NOT AFCI AS REQUIRED BY 210-12. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL; | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | ] |
|