| Plan Review Notes For Permit 02040084 |
| Permit Number |
02040084 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-15 00:00:00 | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER 2001 FBC, MECHANICAL 403.3. & | | | TABLE 403.3.PLEASE NOTE OUTSIDE | | | AIR SHALL NOT BE TAKEN FROM ROOF, | | | ATTIC, OR CRAWLSPACE AS PER 2001 FBC | | | CHAPTER 13 609.1ABC.1. | | | | | | 2.PRESSURE DIFFERENTIALS ACROSS CLOSED | | | DOORS WHERE RETURNS ARE CENTRALLY | | | LOCATED SHALL BE LIMITED TO .001 | | | INCH WC OR LESS.PROVIDE AIR DUCT | | | PATHWAYS OR AIR TRANSFER PATHWAYS | | | FROM THE HIGH PRESSURE ZONE TO THE | | | LOW ZONE. | | | | | | 3.PLEASE CLARIFY RETURN IN THE LAUNDRY | | | ROOM.PLAN DOES NOT REFLECT THE | | | RETURNS BEING DUCTED TO THE AHU. | | | | | | 4.CONDENSATE TERMINATION NOT INDICATED | | | ON PLAN AS PER 2001 FBC 1503.4.4, | | | CONDENSATE SHALL DISCHARGE A MINIMUM | | | OF 12" FROM THE BUILDING STRUCTURE. | | | | | | 5.SEE ALSO ELECTRICAL PLANS REVIEW | | | NOTES #10 & 22. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|