Plan Review Notes
Plan Review Notes For Permit 02040084
Permit Number 02040084
Review Stop M
Sequence Number 1
Notes
Date Text
2002-04-15 00:00:00PLEASE PROVIDE THE FOLLOWING INFORMATION
  
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC, MECHANICAL 403.3. &
 TABLE 403.3.PLEASE NOTE OUTSIDE
 AIR SHALL NOT BE TAKEN FROM ROOF,
 ATTIC, OR CRAWLSPACE AS PER 2001 FBC
 CHAPTER 13 609.1ABC.1.
  
 2.PRESSURE DIFFERENTIALS ACROSS CLOSED
 DOORS WHERE RETURNS ARE CENTRALLY
 LOCATED SHALL BE LIMITED TO .001
 INCH WC OR LESS.PROVIDE AIR DUCT
 PATHWAYS OR AIR TRANSFER PATHWAYS
 FROM THE HIGH PRESSURE ZONE TO THE
 LOW ZONE.
  
 3.PLEASE CLARIFY RETURN IN THE LAUNDRY
 ROOM.PLAN DOES NOT REFLECT THE
 RETURNS BEING DUCTED TO THE AHU.
  
 4.CONDENSATE TERMINATION NOT INDICATED
 ON PLAN AS PER 2001 FBC 1503.4.4,
 CONDENSATE SHALL DISCHARGE A MINIMUM
 OF 12" FROM THE BUILDING STRUCTURE.
  
 5.SEE ALSO ELECTRICAL PLANS REVIEW
 NOTES #10 & 22.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.