2002-04-12 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT SERVICE
 ENTRANCE CONDUCTORS ARE SHOWN AS 2/0`S
 ON RISER DIAGRAM AND NEED TO MEET MIN
 PER 310-15.
  
 2)NOTE: PLEASE NOTE THAT THERE IS AN
 EQUIPMENT GROUNDING BETWEENMETER AND
 MAIN. THIS IS PARALLELING THE NEUTRAL
 WHICH IS NOT PERMITTED.
 PLEASE NOTE THAT THE EQUIPMENT GROUNDING
 CONDUCTOR IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE NOTE THAT SUB PANEL IS
 SHOWN AS 25AMP? PLEASE CLARIFY?
  
 4)NOTE: PLEASE NOTE THAT PANEL "A" IS
 SHOWING #12 1-POLE 50 FEEDING SUB PANEL.
 PLEASE CORRECT.
  
 5)NOTE: PLEASE CLARIFY 220V OUTLET SHOWN
 IN THE MIDDLE OF THE YARD?
  
 6)NOTE: PLEASE NOTE THAT LOCATION OF
 PANEL "A" DOES NOT MEET 110-26.
 PLEASE CHANGE LOCATION TO MEET 110-26.
  
 7)NOTE: PLEASE SHOW LOCATION OF PANEL
 "B".
  
 8)NOTE: PLEASE NOTE MISSING EGRESS
 LIGHTING IN CLOSET (FUTURE BATH) UPSTAIR
 -S. 210-70.
  
 9 ) NOTE: PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
 MISSING.
  
 10NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 11)NOTE: PLEASE NOTE THAT OUTLET
 SPACING NEEDS TO MEET 210-52C -1.
  
 12)NOTE: PLEASE NOTE OUTLET(S) IN GARAGE
 NEEDS TO BE GFI/GFI PROTECTED.
  
 13)NOTE: PLEASE NOTE MISSING OUTLET IN
 BEDROOM. PER 210-52.
  
 14)NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 15)NOTE: PLEASE NOTE THAT PANEL IS SHOWN
 AS MLO? PLEASE CLARFIY WHERE MAIN DISC
 IS. PER 225-31
  
 16)NOTE: PLEASE CLARFIY HOW THERE ARE
 CIRCUITS SHOWN AS SMALL APPL AND DINING
 AND SM APPL AND LAUNDRY. PLEASE NOTE
 THESE CIRCUITS CAN NOT BE COMBINED,
 PER 210-52,210-11
  
 17)NOTE: PLEASE NOTE THAT LOADS SHOWN
 FOR AHU`S ARE SHOWN AT 16KW AND 17KW
 ONCALCS? PLEASE CLARIFY.
  
 18)NOTE: PLEASE NOTE THAT LOAD CALCS
 FOR PANEL "B" ARE SHOWING LOAD FOR "B"
 AT 206A`S??? PLEASE CORRECT.
  
 19)NOTE: PLEASE NOTE THAT IF THERE IS
 GOING TO BE ANY LOW VOLTAGE CATV, OR
 TELEPHONE, THEN THIS NEEDS TO BE SHOWN
 ON PLANS.
  
 20)NOTE: PLEASE VERFIY LOCATION SHOWN
 FOR BOTH AHU`S. PLEASE VERIFY FOR
 CLEARENCES, AND LOCATION OF RETURNS.
 110-26
 21)NOTE: PLEASE SHOW WHERE/WHAT EGRESS
 LIGHTING MEANS WILL BE FOR STAIRS UP TO
 ROOF.210-70
  
 22)NOTE: PLEASE NOTE THAT DISC`S AHU`S
 AND CU`S NEED TO MEET 110-26.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372