| 2002-04-12 00:00:00 | ***************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT SERVICE |
| | ENTRANCE CONDUCTORS ARE SHOWN AS 2/0`S |
| | ON RISER DIAGRAM AND NEED TO MEET MIN |
| | PER 310-15. |
| | |
| | 2)NOTE: PLEASE NOTE THAT THERE IS AN |
| | EQUIPMENT GROUNDING BETWEENMETER AND |
| | MAIN. THIS IS PARALLELING THE NEUTRAL |
| | WHICH IS NOT PERMITTED. |
| | PLEASE NOTE THAT THE EQUIPMENT GROUNDING |
| | CONDUCTOR IS ONLY INSTALLED AFTER THE |
| | FIRST MEANS OF DISCONNECT. |
| | |
| | 3)NOTE: PLEASE NOTE THAT SUB PANEL IS |
| | SHOWN AS 25AMP? PLEASE CLARIFY? |
| | |
| | 4)NOTE: PLEASE NOTE THAT PANEL "A" IS |
| | SHOWING #12 1-POLE 50 FEEDING SUB PANEL. |
| | PLEASE CORRECT. |
| | |
| | 5)NOTE: PLEASE CLARIFY 220V OUTLET SHOWN |
| | IN THE MIDDLE OF THE YARD? |
| | |
| | 6)NOTE: PLEASE NOTE THAT LOCATION OF |
| | PANEL "A" DOES NOT MEET 110-26. |
| | PLEASE CHANGE LOCATION TO MEET 110-26. |
| | |
| | 7)NOTE: PLEASE SHOW LOCATION OF PANEL |
| | "B". |
| | |
| | 8)NOTE: PLEASE NOTE MISSING EGRESS |
| | LIGHTING IN CLOSET (FUTURE BATH) UPSTAIR |
| | -S. 210-70. |
| | |
| | 9 ) NOTE: PLEASE NOTE FRONT AND REAR |
| | RECEPTS REQ`D PER 210-52E |
| | MISSING. |
| | |
| | 10NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | A/C EQUIPMENT. PER 210-63 AND/OR SECTION |
| | 306 OF THE MECHANICAL CODE. |
| | |
| | 11)NOTE: PLEASE NOTE THAT OUTLET |
| | SPACING NEEDS TO MEET 210-52C -1. |
| | |
| | 12)NOTE: PLEASE NOTE OUTLET(S) IN GARAGE |
| | NEEDS TO BE GFI/GFI PROTECTED. |
| | |
| | 13)NOTE: PLEASE NOTE MISSING OUTLET IN |
| | BEDROOM. PER 210-52. |
| | |
| | 14)NOTE: PLEASE LIST THE REQ`D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE. PER 210-12 |
| | |
| | 15)NOTE: PLEASE NOTE THAT PANEL IS SHOWN |
| | AS MLO? PLEASE CLARFIY WHERE MAIN DISC |
| | IS. PER 225-31 |
| | |
| | 16)NOTE: PLEASE CLARFIY HOW THERE ARE |
| | CIRCUITS SHOWN AS SMALL APPL AND DINING |
| | AND SM APPL AND LAUNDRY. PLEASE NOTE |
| | THESE CIRCUITS CAN NOT BE COMBINED, |
| | PER 210-52,210-11 |
| | |
| | 17)NOTE: PLEASE NOTE THAT LOADS SHOWN |
| | FOR AHU`S ARE SHOWN AT 16KW AND 17KW |
| | ONCALCS? PLEASE CLARIFY. |
| | |
| | 18)NOTE: PLEASE NOTE THAT LOAD CALCS |
| | FOR PANEL "B" ARE SHOWING LOAD FOR "B" |
| | AT 206A`S??? PLEASE CORRECT. |
| | |
| | 19)NOTE: PLEASE NOTE THAT IF THERE IS |
| | GOING TO BE ANY LOW VOLTAGE CATV, OR |
| | TELEPHONE, THEN THIS NEEDS TO BE SHOWN |
| | ON PLANS. |
| | |
| | 20)NOTE: PLEASE VERFIY LOCATION SHOWN |
| | FOR BOTH AHU`S. PLEASE VERIFY FOR |
| | CLEARENCES, AND LOCATION OF RETURNS. |
| | 110-26 |
| | 21)NOTE: PLEASE SHOW WHERE/WHAT EGRESS |
| | LIGHTING MEANS WILL BE FOR STAIRS UP TO |
| | ROOF.210-70 |
| | |
| | 22)NOTE: PLEASE NOTE THAT DISC`S AHU`S |
| | AND CU`S NEED TO MEET 110-26. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE NAY QUESTIONS, |
| | PLEASE CALL. |
| | |