Plan Review Notes
Plan Review Notes For Permit 02040084
Permit Number 02040084
Review Stop B
Sequence Number 1
Notes
Date Text
2002-05-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FBC* 104.2.1.3THE USE OF 'WITE-OUT'
 ON PLANS SUBMITTED FOR PERMITTING
 PURPOSES IS INAPPROPRIATE.THE
 RESUBMITTED PLANS MUST NOT INCLUDE
 ALTERATIONS MADE WITH CORRECTION FLUID.
  
 4) SHEET A-12, SPECIFICATIONS.
 2.02 MAKES REFERENCETO THE VILLAGE OF
 PALM BEACH.CORRECT THIS TO READ CITY
 OF WEST PALM BEACH.
 6.13, 6.15B & H, AND 7.01 ALL MAKE
 REFERENCE TO STANDARD BUILDING CODE.
 SHEETS S-1 AND S-2 MAKE REFERENCE TO
 SOUTH FLORIDA BUILDING CODE.CORRECT
 ALL BUILDING CODE REFERENCES TO 'FLORIDA
 BUILDING CODE 2001'.
  
 5) FBC 1606.1.6SHEET S-0 REFERS TO A
 WIND SPEED OF 110MPH.THAT WAS THE WIND
 SPEED UNDER THE STANDARD BUILDING CODE.
 THE CORRECT WIND SPEED, UNDER THE
 FLORIDA BUILDING CODE, IS 140MPH.
  
 6) PRODUCT APPROVAL NOTICE OF ACCEPTANCE
 NO. 99-0223.07 STATES THAT THE FIBER
 CEMENT SIDING SHALL BE INSTALLED OVER A
 5/8" PLYWOOD SUBSTRATE.DETAILS A-9/6,7
 AND 9 DO NOT REFLECT THIS.ANNOTATE THE
 PLANS TO ENSURE COMPLIANCE WITH THE
 REQUIREMENT OF THE PRODUCT APPROVAL AND
 TO CORRELATE WITH DETAIL S-4/1.
  
 7) PRODUCT APPROVAL NOTICE OF ACCEPTANCE
 NO. 02-0205.07 INDICATES THAT THE DOUBLE
 FRENCH DOOR ARRANGEMENT REQUIRES AN
 ASTRAGAL BETWEEN THE TWO DOOR LEAFS.
 THIS REQUIREMENT IS NOT REFLECTED ON THE
 FLOOR PLANS.AMEND THE PLANS OR SUBMIT
 A PRODUCT APPROVAL THAT CORRESPONDS TO
 THE PROPOSED ARRANGEMENT.
  
 8) ELEVATION SHEETS A-5 AND A-6 SHOW
 SINGLE HUNG WINDOWS.THE SUBMITTED
 PRODUCT APPROVALS ARE FOR FIXED WINDOWS
 AND CASEMENT WINDOWS.SUBMIT A PRODUCT
 APPROVAL TO COVER THE PROPOSED WINDOW
 TYPE.
  
 9) DOOR AND WINDOW SCHEDULE SHEET A-11
 REFERS TO HURRICANE MISSILE IMPACT
 PROTECTION SHUTTERS FOR SOME WINDOWS.
 SUBMIT A PRODUCT APPROVAL FOR THE
 PROPOSED SHUTTERS.
  
 10) FBC 1606.3.2SUBMIT A PRODUCT
 APPROVAL FOR THE ROOF COVERING.
  
 11) FBC 2309.6EACH OF THE ATTIC SPACES
 SHALL BE PROVIDED WITH ACCESS OPENINGS
 NOT LESS THAN 20"X36".
  
 12) FBC 2405.2THE GLAZING IN THE DOORS
 AND GLAZED PANELS WITHIN 24" OF A DOOR
 IS IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 13) FBC 1007.8.2DETAILS OF THE
 CIRCULAR STAIRWAYS SHALL BE SUBMITTED
 BEFORE CONSTRUCTION.
  
 14) FBC 1608.2.2GUARDRAILS.SUBMIT
 GUARDRAIL ATTACHMENT DETAILS, FOR EACH
 OF THE BALCONIES, TO DEMONSTRATE
 COMPLIANCE WITH THE LOADING REQUIREMENTS
  
 15) FBC* 104.2.1.2SHEET S-2, HIGH ROOF
 FRAMING PLAN.THE CORNER COLUMN C-4 AND
 ASSOCIATED BEAM B-8 WILL RECEIVE LOAD
 FROM THE REAR JACUZZI, VIA THE PRE-
 MANUFACTURED ROOF TRUSSES, IN ADDITION
 TO GENERAL ROOF/TERRACE LOAD. STRUCTURAL
 CALCULATION SHEET 17 DOES NOT ACCOUNT
 FOR THIS.SUBMIT ADDITIONAL DETAILS TO
 DESCRIBE THE LOAD PATH DOWN TO FIRST
 FLOOR.ALSO, WHAT SUPPORTS BEAM B-3?
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499