2002-04-03 00:00:00 
 PROVISO SHOW COMPLIANCE WITH AIR BALANCE
 AND LOCATION OF DUCTS AT THE TIME OF
 INSPECTION.
  
 2001 FLORIDA BUILDING CODE.
  
 AS PER 2001 FBC, MECHANICAL 601.4,
 BALANCED RETURN AIR REQUIRED.PRESSURE
 DIFFERNETIALS ACROSS DOORS WHERE
 RETURNS ARE CENTERALLY LOCATED SHALL BE
 LIMITED TO .001 INCH WC.PROVED AIR
 DUCT PATHWAYS OR AIR TRANSFER PATHWAYS
 FROM HIGH PRESSURE ZONE TO THE LOW ZONE.
  
 DUCTS SHALL NOT BE INSTALLED IN OR
 WITHIN 6 INCHES OF EARTH AS PER 603.7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388