Plan Review Notes
Plan Review Notes For Permit 02040076
Permit Number 02040076
Review Stop P
Sequence Number 1
Notes
Date Text
2002-04-29 00:00:00DENIED;
 1.MINIMUM PLUMBING FACILITIES TABLE
 403.1. SERVICE SINK IS REQUIRED.
 2.PAGE 3 WASTE RISER DIAGRAM. STERILIZER
 SHALL BE AN INDIRECT WASTE SEC 713.3.
 A.PROCESSOR SHOWN DISCHARGING INTO
 SANITARY SYSTEM BUT NOTE 11 STATES
 WASTE SHALL NOT DISCHARGE TO
 SANITARY, ALSO SHOW BACKFLOW
 PROTECTION. PROVIDE MANUFACTORS
 CUT SHEETS.
 B.VACUUM SYSTEM TO DISCHARGE TO
 SANITARY, NOT SHOWN ON PLAN.
 3.WATER HAMMER ARRESTORS ARE REQUIRED
 AND INSTALLED PER SEC 604.9 AND
 MANUFACTORS SPECIFACTIONS.
 4.SHOW LOCATION OF BACKFLOW PREVENTOR.
 IF INSIDE THE BUILDING A A DRAIN WILL
 BE REQUIED.
 5.MED. GAS (VAC. & AIR)
 SEPARATE PERMIT REQUIRED COTRACTOR
 TO BE A CERTIFIED MED GAS INSTALLER.
 6.EQUIPMENT SPECS. REQUIRED FOR
 COMPRESSOR AND VACUUM SYSTEMS SHOW
 PIPE SIZES, CLEANOUT. US NFPA 99A
 LEVEL 3 FOR INSTALLATION REQUIREMENTS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved