| Plan Review Notes For Permit 02040076 |
| Permit Number |
02040076 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-29 00:00:00 | DENIED; | | | 1.MINIMUM PLUMBING FACILITIES TABLE | | | 403.1. SERVICE SINK IS REQUIRED. | | | 2.PAGE 3 WASTE RISER DIAGRAM. STERILIZER | | | SHALL BE AN INDIRECT WASTE SEC 713.3. | | | A.PROCESSOR SHOWN DISCHARGING INTO | | | SANITARY SYSTEM BUT NOTE 11 STATES | | | WASTE SHALL NOT DISCHARGE TO | | | SANITARY, ALSO SHOW BACKFLOW | | | PROTECTION. PROVIDE MANUFACTORS | | | CUT SHEETS. | | | B.VACUUM SYSTEM TO DISCHARGE TO | | | SANITARY, NOT SHOWN ON PLAN. | | | 3.WATER HAMMER ARRESTORS ARE REQUIRED | | | AND INSTALLED PER SEC 604.9 AND | | | MANUFACTORS SPECIFACTIONS. | | | 4.SHOW LOCATION OF BACKFLOW PREVENTOR. | | | IF INSIDE THE BUILDING A A DRAIN WILL | | | BE REQUIED. | | | 5.MED. GAS (VAC. & AIR) | | | SEPARATE PERMIT REQUIRED COTRACTOR | | | TO BE A CERTIFIED MED GAS INSTALLER. | | | 6.EQUIPMENT SPECS. REQUIRED FOR | | | COMPRESSOR AND VACUUM SYSTEMS SHOW | | | PIPE SIZES, CLEANOUT. US NFPA 99A | | | LEVEL 3 FOR INSTALLATION REQUIREMENTS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT 8369 |
|