1 |
|
| Notes |
| Date |
Text |
| 2002-04-18 00:00:00 | 2001 FLORIDA BUIDLING CODE, MECHANICAL | | | | | | 1.PLEASE PROVIDE OUTSIDE AIR | | | CALCULATIONS AS PER 2001 FBC(M) OR | | | ASHRAE 62-89. | | | | | | 2.PROVIDE MANUFACTURER INFORMATION FOR | | | THE HVAC EQUIPMENT AS WELL AS ANY | | | EXHAUST FANS. | | | | | | 3.INDICATE DUCT MATERIAL, SIZE AND CFM | | | DISTRIBUTION. | | | | | | 4.INDICATE GRILLE SIZE.PLEASE NOTE | | | AS PER 2001 FBC(M) 603.15, BALANCING | | | DAMPERS OR OTHER MEANS OF SUPPLY AIR | | | ADJUSTMENT SHALL BE PROVIDED IN THE | | | BRANCH DUCTS OR AT EACH INDIVIDUAL | | | DUCT REGISTER, GRILLE OR DIFFUSER. | | | | | | 5.INDICATE CONDENSATE DRAIN SIZE AND | | | TERMINATION. | | | | | | 6.SHOULD CONDENSERS BE LOCATED ON THE | | | ROOF, PROVIDE MANUFACTURER SUBMITTAL | | | DATA FOR THE STAND. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|