2002-04-18 00:00:002001 FLORIDA BUIDLING CODE, MECHANICAL
  
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS AS PER 2001 FBC(M) OR
 ASHRAE 62-89.
  
 2.PROVIDE MANUFACTURER INFORMATION FOR
 THE HVAC EQUIPMENT AS WELL AS ANY
 EXHAUST FANS.
  
 3.INDICATE DUCT MATERIAL, SIZE AND CFM
 DISTRIBUTION.
  
 4.INDICATE GRILLE SIZE.PLEASE NOTE
 AS PER 2001 FBC(M) 603.15, BALANCING
 DAMPERS OR OTHER MEANS OF SUPPLY AIR
 ADJUSTMENT SHALL BE PROVIDED IN THE
 BRANCH DUCTS OR AT EACH INDIVIDUAL
 DUCT REGISTER, GRILLE OR DIFFUSER.
  
 5.INDICATE CONDENSATE DRAIN SIZE AND
 TERMINATION.
  
 6.SHOULD CONDENSERS BE LOCATED ON THE
 ROOF, PROVIDE MANUFACTURER SUBMITTAL
 DATA FOR THE STAND.
  