2002-04-25 00:00:00***************** UNSAT ****************
  
  
 1)NOTE: PLEASE NOTE THAT THE CODE ARTS
 REF ARE STILL FROM 96 NEC. PLEASE
 MAKE CHANGES TO REFLECT 99 NEC.
  
 2 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 3)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  