Plan Review Notes
Plan Review Notes For Permit 02040047
Permit Number 02040047
Review Stop P
Sequence Number 1
Notes
Date Text
2002-04-21 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 PRIVATE POOLS
  
 1) PLEASE ADJUST GENERAL NOTES AND DE-
 TAILS AS FOLLOWS.
 A) PLEASE SHOW SLAB TO BE NOMINAL 4 INCH
 THICK.
 B)
 FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 C)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 D)
 FBC-2001 SEC 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 E)
 FBC-2001 SEC 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
 2) FOR FUTURE REFERENCE THE FOLLOWING
 INFORMATION REQUIRED ON PLANS WHEN A
 POOL HEATER IS INSTALLED.
 A)
 FBC-2001 SEC 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 B)
 FBC-2001 SEC 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 C)
 FBC-2001 SEC 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 D)
 FBC-2001 SEC 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377