Plan Review Notes
Plan Review Notes For Permit 02031914
Permit Number 02031914
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-29 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS AND LARGEST MOTOR LOADS AT 125%.
 PLEASE NOTE THAT LOAD CALCUALTIONS NEED
 TO BE SHOWN. 215-2/3, 230-42, 430 ETC.
  
 2)NOTE: PLEASE NOTE THAT GFI PROETCION
 FOR ALL SUBMERSIBLE PUMPS. 680-51
  
 3)NOTE: PLEASE NOTE COLOR CODING OF 277V
 /480V PER LOCAL AMENDMENTS.215-2
 BROWN/ PURPLE/ YELLOW.
  
 4)NOTE: PLEASE NOTE THAT MEANS OF
 CONTROLLING OF LIGHTS IN PUMP ROOM ALSO,
 NOT JUST AT THE TOP OF THE STAIRS
 OUTSIDE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
 PLEASE NOTE WRONG BLDG CODE REFERENCED,
 SHOWS 1997 AND SHOULD BE 2001.