| Plan Review Notes For Permit 02031914 |
| Permit Number |
02031914 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-29 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS AND LARGEST MOTOR LOADS AT 125%. | | | PLEASE NOTE THAT LOAD CALCUALTIONS NEED | | | TO BE SHOWN. 215-2/3, 230-42, 430 ETC. | | | | | | 2)NOTE: PLEASE NOTE THAT GFI PROETCION | | | FOR ALL SUBMERSIBLE PUMPS. 680-51 | | | | | | 3)NOTE: PLEASE NOTE COLOR CODING OF 277V | | | /480V PER LOCAL AMENDMENTS.215-2 | | | BROWN/ PURPLE/ YELLOW. | | | | | | 4)NOTE: PLEASE NOTE THAT MEANS OF | | | CONTROLLING OF LIGHTS IN PUMP ROOM ALSO, | | | NOT JUST AT THE TOP OF THE STAIRS | | | OUTSIDE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | | | | PLEASE NOTE WRONG BLDG CODE REFERENCED, | | | SHOWS 1997 AND SHOULD BE 2001. |
|