Plan Review Notes
Plan Review Notes For Permit 02031844
Permit Number 02031844
Review Stop B
Sequence Number 1
Notes
Date Text
2002-05-06 00:00:00PERMIT APPLICATIONS SUBMITTED SUBSEQUENT
 TO MARCH 1, 2002 MUST COMPLY WITH THE
 2001 FLORIDA BUILDING CODE.THE PLANS
 DECLARE 1997 SBC.HOW WERE THE
 FRACTIONAL WIND PRESSURES SHOWN ON
 SHEET 3 OF 3 DETERMINED?
  
 THE EXISTING BEDROOM MUST COMPLY WITH
 THE EMERGENCY EGRESS REQUIREMENTS OF
 FBC 1005.4.
  
 THE METRO DADE REPORTS FOR THE CLOPAY
 GARAGE DOOR AND THE PGT CASEMENT WINDOW
 HAVE ILLEGIBLE DRAWINGS.PLEASE PROVIDE
 CLEAR COPIES.
  
 THE ADDITION IS SUBJECT TO IMPACT FEES
 COLLECTED BY THE COUNTY FOR THE CITY.
 THE PERMIT PLANS MUST BE STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.