Plan Review Notes
Plan Review Notes For Permit 02031690
Permit Number 02031690
Review Stop P
Sequence Number 1
Notes
Date Text
2002-04-30 00:00:00DENIED;
 1.WOMENS TOILET ROOM DOES NOT MEET
 MINIMUM INSIDE WIDTH.
 2.URINAL TO MEET FACBC REQUREMENTS SEE
 SEC 11-4.18.1 THRU11-4.18.4. SHOW
 DETAIL ON DRAWING.
 3.GREASE TRAP TO BE SIZED AND LOCATED BY
 RODNEY COMPO UTILITY DEPARTMENT PHONE
 837-4074 SPECIFICATIONS WILL BE
 REQUIRED, SIZE MANUFACTOR, CERTIFIED
 BY ETC.
 4.ALL INDIRECT WASTE TO FLOOR SINKS ICE
 MAKER, SODA DISPENSOR ETC.
 5.HOT WATER TO HAND SINKS AND LAVITORIES
 TO BE 110 DEG. IF HOTTER WATER IS
 REQUIRED FOR 3 COMPARTMENT SINK SHOW
 TEMPORING VALVE.
 6.SHOCK ARRESTORS REQUIRED WITH SEC.
 604.9.
 7.PAGE M2.0 RISER DIAGRAM. SHOW CLEAR
 SEPORATION OF GREASY WASTE AND
 SANITARY PIPING. W/C AND URINAL CANNOT
 GO THRU GREASE TRAP.
 8.WHAT TYPE FIXTURE IS ABOVE URINAL. NOT
 MARKED.
 9.FLOOR DRAINS REQUIRED WITH TRAP PRIMER
 IN REST ROOMS.
  
 10.RISER DIAGRAM SHOWS 3 LAVS AND 3 W/C
 AND MISSING SERVICE SINK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369