| Plan Review Notes For Permit 02031690 |
| Permit Number |
02031690 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-30 00:00:00 | DENIED; | | | 1.WOMENS TOILET ROOM DOES NOT MEET | | | MINIMUM INSIDE WIDTH. | | | 2.URINAL TO MEET FACBC REQUREMENTS SEE | | | SEC 11-4.18.1 THRU11-4.18.4. SHOW | | | DETAIL ON DRAWING. | | | 3.GREASE TRAP TO BE SIZED AND LOCATED BY | | | RODNEY COMPO UTILITY DEPARTMENT PHONE | | | 837-4074 SPECIFICATIONS WILL BE | | | REQUIRED, SIZE MANUFACTOR, CERTIFIED | | | BY ETC. | | | 4.ALL INDIRECT WASTE TO FLOOR SINKS ICE | | | MAKER, SODA DISPENSOR ETC. | | | 5.HOT WATER TO HAND SINKS AND LAVITORIES | | | TO BE 110 DEG. IF HOTTER WATER IS | | | REQUIRED FOR 3 COMPARTMENT SINK SHOW | | | TEMPORING VALVE. | | | 6.SHOCK ARRESTORS REQUIRED WITH SEC. | | | 604.9. | | | 7.PAGE M2.0 RISER DIAGRAM. SHOW CLEAR | | | SEPORATION OF GREASY WASTE AND | | | SANITARY PIPING. W/C AND URINAL CANNOT | | | GO THRU GREASE TRAP. | | | 8.WHAT TYPE FIXTURE IS ABOVE URINAL. NOT | | | MARKED. | | | 9.FLOOR DRAINS REQUIRED WITH TRAP PRIMER | | | IN REST ROOMS. | | | | | | 10.RISER DIAGRAM SHOWS 3 LAVS AND 3 W/C | | | AND MISSING SERVICE SINK. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|