| 2002-04-10 00:00:00 | | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER 2001 FBC, MECHANICAL TABLE | | | 403.3 OR ASHRAE 62-89. | | | | | | 2.PROVIDE MANUFACTURER SUBMITTAL DATA | | | OVEN. | | | | | | 3.PROVIDE MANUFACTURER INFORMATION | | | FOR THE NEW 4 TON RTU. (MAKE, MODEL | | | BTU, SEER). | | | | | | 4.INDICATE CFM DISTRIBUTION ON PLAN. | | | | | | 3.ADDITIONAL PERMITS REQUIRED FOR WALK | | | IN FREEZER/COOLER, HOOD AND FIRE | | | SUPRESSION.PLEASE PROVIDE PLANS & | | | MANUFACTURER SUBMITTAL DATA WITH | | | PERMIT APPLILCATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|