Plan Review Notes
Plan Review Notes For Permit 02031690
Permit Number 02031690
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-11 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT TWO DIFFERENT
 E-SHEETS WERE SUBMITTED? PLEASE NOTE
 THAT BOTH HAVE THE SAME DATE AND ARE
 NOT DATED BY ARCH? PLEASE ONLY SUBMIT
 THE LATEST ONE TO BE REVIEWED.
  
 2)NOTE: PLEASE NOTE THAT ALL BRANCH
 CIRCUITING #`S ARE TO BE SHOWN ON PLANS
 AND CORRELATE WITH A SUBMITTED PANEL
 SCHEDULE.
  
 3)NOTE: PLEASE SHOW SIZE OF EXISTING
 PANEL IN ORDER TO VERIFY LOAD TO SERVICE
 SIZE.
  
 4)NOTE: PLEASE NOTE MISSING SHOW WINDOW
 OUTLETS PER 210-62
  
 5)NOTE: PLEASE CLARIFY REQ`D SIGN
 CIRCUIT PER 600-5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372