| Plan Review Notes For Permit 02031690 |
| Permit Number |
02031690 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-11 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT TWO DIFFERENT | | | E-SHEETS WERE SUBMITTED? PLEASE NOTE | | | THAT BOTH HAVE THE SAME DATE AND ARE | | | NOT DATED BY ARCH? PLEASE ONLY SUBMIT | | | THE LATEST ONE TO BE REVIEWED. | | | | | | 2)NOTE: PLEASE NOTE THAT ALL BRANCH | | | CIRCUITING #`S ARE TO BE SHOWN ON PLANS | | | AND CORRELATE WITH A SUBMITTED PANEL | | | SCHEDULE. | | | | | | 3)NOTE: PLEASE SHOW SIZE OF EXISTING | | | PANEL IN ORDER TO VERIFY LOAD TO SERVICE | | | SIZE. | | | | | | 4)NOTE: PLEASE NOTE MISSING SHOW WINDOW | | | OUTLETS PER 210-62 | | | | | | 5)NOTE: PLEASE CLARIFY REQ`D SIGN | | | CIRCUIT PER 600-5. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|