| Notes |
| Date |
Text |
| 2002-04-20 00:00:00 | DENIED | | | REFERENCE: SPC-94 | | | | | | 1) SHT P-1 WATER HEATER DETAIL, 1" PAN | | | DRAIN REQUIRED. | | | 2) SHT P-2 DRAIN PAN DETAIL, 1" PAN | | | DRAIN REQUIRED. | | | 3) SHT P-3 WATER RISER DIAGRAM, AIR | | | CHAMBERS ARE A QUICK FIX AND DO NOT WORK | | | BUT IF USED THEY SHALL BE ACCESSIBLE AND | | | RECHARGEABLE PER SEC 607.8.3. (SEE ATT- | | | ACHED SHEETS FOR APPROVED AIR CHAMBER) | | | APPROVED WATER HAMMER ARRESTORS DO NOT | | | REQUIRE ACCESS AND DO NOT REQUIRE SERV- | | | ICE AND IF USED THEY SHALL BE LOCATED IN | | | AN "EFFECTIVE RANGE" CLOSE TO FIXTURE | | | NOT AT TOP OF DROP. THIS IS TYPICAL ON | | | SHTS P-4, P-5, & P-6 ALSO. | | | 4) SHT P-4 SANITARY RISER DIAGRAM, 3RD | | | FLOOR BATHROOM SHALL BE TAKEN OFF STACK | | | BELOW KITCHEN SINK. THIS IS TYPICAL ON | | | SHT P-5, SHT P-6 AND P-7 AT WASH MACHINE | | | 5) SHT P-4 SANITARY RISER DIAGRAM, | | | PIPING BELOW 2ND FLOOR CONFUSING. SEEMS | | | THE 3" RUNS INTO A TEE WITH FLOW COMMING | | | FROM TWO DIRECTIONS. THEN WHEN IT SHOULD | | | TURN TO THE WASH MACHINE IT TEES AGAIN. | | | WHERE DOES THE PIPE TO THE RIGHT OF THE | | | TEE GO?? | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|