| 2002-05-02 00:00:00 | 1) SITE PLAN DOES NOT INDICATE FIRE |
| | HYDRANT LOCATIONS. PLEASE INDICATE FIRE |
| | HYDRANT LOCATIONS ON SITE PLAN. WET |
| | FIRE HYDRANTS ARE REQUIRED PRIOR TO, |
| | DURING AND AFTER CONSTRUCTION. |
| | 2) BUILDING ADDRESSES REQUIRED ON THE |
| | TOWNHOUSES. NUMBERS ARE TO BE AT LEAST |
| | 3" HIGH. |
| | 3) ELECTRIC POWERED SMOKE DETECTORS |
| | SHALL BE INSTALLED OUTSIDE EVERY |
| | SLEEPING AREA IN THE IMMEDIATE VICINITY |
| | OF THE BEDROOMS AND ALL LEVELS OF THE |
| | DWELLING. |
| | 4) STORAGE UNDER STAIRS NOT ALLOWED. IF |
| | ALLOWED, STORAGE AREA TO BE AT LEAST |
| | ONE HOUR FIRE RATED. |
| | 5) NFPA 1 DEFINES "THAT WHEREVER THERE |
| | ARE THREE OR MORE LIVING UNITS IN A |
| | BUILDING, THE BUILDING IS CONSIDERED AN |
| | APARTMENT BUILDING. THE FIRE SPRINKLER |
| | SYSTEMS IN THESE UNITS MUST BE 13R |
| | TYPES. |
| | 6) PLEASE PROVIDE PRESCRIPTIVE CODE |
| | REQUIREMENTS FOR THE BALCONY RAILINGS. |
| | 7) NO FIRE DEPARTMENT CONNECTION COULD |
| | BE LOCATED FOR BUILDING 6. |
| | 8) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE SPRINKLER SYSTEMS. |
| | 9) PLEASE EXPLAIN VOID UNDER STAIRS. |
| | 10) PLEASE EXPLAIN 10" TREADS. NEW |
| | STAIRS ARE TO HAVE 11" TREADS. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |