Plan Review Notes
Plan Review Notes For Permit 02031545
Permit Number 02031545
Review Stop P
Sequence Number 2
Notes
Date Text
2002-06-27 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) FROM PREVIOUS REVIEW: SHT P-2 WATER
 HAMMER ARRESTORS SHALL BE REQUIRED FOR
 QUICK CLOSING VALVES AND LOCTED NEAR THE
 FIXTURE IN AN "EFFECTIVE RANGE" NOT AT
 TOP OF DROP AS SHOWN. SEC 604.9
 2) SHT P-2 PLUMBING NOTES #13 AIR
 CHAMBERS NOT APPROVED. DELETE REFERENCE
 3) FROM PREVIOUS REVIEW: TOILET ROOMS
 ARE NOT WIDE ENOUGH. MINIMUM WITH IS
 5'3". SEE SHT A-4 DETAILS ALSO
 4) SHT A-2 SNACK ROOM SINK TO COMPLY
 WITH 11-4.24.1 THRU 11-4.24.7 PLEASE
 PROVIDE DETAILS. FROM PREVIOUS REVIEW.
 ------NEW COMMENTS------
 5) PER TABLE 403.1, A DRINKING FOUNTAIN
 AND A SERVICE SINK IS REQUIRED. PLEASE
 SHOW FIXTURES ON RESUBMITTED PLANS.
 6) PLEASE REMOVE ALL VOIDED/SUPERSEDED
 SHEETS AND PLACE NEW SHEETS IN PLAN FOR
 REVIEW. RESUBMIT ONE SET OF OLD SHEETS
 FOR COMPARISON SEPARATE FROM NEW COMPLE-
 TE SET.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377