 1.AS PER 2001 FMC, OUTSIDE AIR EXHAUST
 AND INTAKE OPENINGS SHALL BE LOCATED
 A MINIMUM OF 10 FT FROM LOT LINES OR
 BUILDINGS ON THE SAME LOT. FBC 401.5
  
 2.FMC 401.5.2, EXHAUST AIR SHALL NOT
 BE DIRECTED ONTO WALKWAYS.
  
 3.SEE FIRE DEPARTMENTS COMMENTS AS TO
 STORAGE WITHIN THE BUILDING.
  
 4.CLARIFY LOCATION AND SEPARATION OF
 THE OUTSIDE AIR IN REFERENCE TO THE
 EHXAUST OF CONDENSERS.
  
 PROVISO:
  
 AS PER 2001 FBC 1503.4.4, CONDENSATE
 SHALL DISCHARGE A MINIMUM OF 12 INCHES
 FROM THE BUILDING STRUCTURE.
  