| Plan Review Notes For Permit 02031545 |
| Permit Number |
02031545 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-11 00:00:00 | A) PLEASE INDICATE WHAT WILL BE STORED | | | WITHIN THE BUILDING. THE PLANS INDICATE | | | S-2 OCCUPANCY. | | | B) PLEASE INDICATE ALL EXIT DOOR | | | LOCATIONS FOR THE BUILDING. THE KEY PLAN | | | COULD REFLECT MULTIPLE TENANT | | | ARRANGEMENT OR A SINGLE TENANT, PLEASE | | | EXPLAIN. | | | C) BUILDING ADDRESS REQUIRED ON | | | BUILDING. | | | D) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION INFORMATION. | | | E) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM REMODEL. | | | F) NO FIRE ALARM EQUIPMENT SHOWN. ARE | | | ANY DEVICES PLANNED FOR THE SPACE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|