| Plan Review Notes For Permit 02031545 |
| Permit Number |
02031545 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-11 00:00:00 | ************ UNSAT ************ | | | | | | 1)NOTE: PLEASE CLARIFY ANY CIRCUITING | | | REQ`D PER 600-5. | | | | | | 2)NOTE: PLEASE CLARIFY ROOM USES. PLEASE | | | LABEL ON PLANS. PLEASE CLARIFY IF ROOM | | | WITH TRACK LIGHTING IS SOME SORT OF | | | "SHOW WINDOW"? | | | PLEASE NOTE 210-62 IF INDEED USED FOR | | | SHOW/DISPLAYING OF ITEMS/GOODS. ART 100. | | | | | | 3)NOTE: PLEASE CLARIFY AHU #1 AND #3 ?? | | | PLEASE NOTE THAT #1 SHOWS 11.5KW AND | | | #3 IS SHOWN WITH THE SAME LOAD AS #1 | | | WITH LESS OCP AND SMALLER WIRE SIZES.?? | | | | | | 4))NOTE: PLEASE NOTE THAT THE LOAD | | | CALCULATIONS NEED TO BE SHOWN. SQ FT/ | | | RECEPT LOADS ETC. PER 220-3,220-10, | | | 220-11, 220-13. (215-5) | | | | | | 5)NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ETC) | | | 215-2,215-3,230-42 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|