Plan Review Notes
Plan Review Notes For Permit 02031545
Permit Number 02031545
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-11 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE CLARIFY ANY CIRCUITING
 REQ`D PER 600-5.
  
 2)NOTE: PLEASE CLARIFY ROOM USES. PLEASE
 LABEL ON PLANS. PLEASE CLARIFY IF ROOM
 WITH TRACK LIGHTING IS SOME SORT OF
 "SHOW WINDOW"?
 PLEASE NOTE 210-62 IF INDEED USED FOR
 SHOW/DISPLAYING OF ITEMS/GOODS. ART 100.
  
 3)NOTE: PLEASE CLARIFY AHU #1 AND #3 ??
 PLEASE NOTE THAT #1 SHOWS 11.5KW AND
 #3 IS SHOWN WITH THE SAME LOAD AS #1
 WITH LESS OCP AND SMALLER WIRE SIZES.??
  
 4))NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN. SQ FT/
 RECEPT LOADS ETC. PER 220-3,220-10,
 220-11, 220-13. (215-5)
  
 5)NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
 215-2,215-3,230-42
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICL PLAN REVIEW
 561-659-8096 EXT 8372