| Plan Review Notes For Permit 02031487 |
| Permit Number |
02031487 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-04 00:00:00 | A) WRONG LIFE SAFETY CODE REFERENCED | | | ON THE PLANS. SHOULD READ FLORIDA | | | FIRE PREVENTION CODE, 2000 EDITION | | | OF THE LIFE SAFETY CODE. | | | B) ANY SECURITY FEATURES PLANNED FOR THE | | | DOORS MUST COMPLY WITH "SPECIAL LOCKING | | | ARRANGEMENTS" FROM THE LIFE SAFETY CODE. | | | ANY LOCKS INSTALLED MUST MEET EITHER | | | "DELAYED EGRESS LOCKS" OR " ACCESS | | | CONTROLLED EGRESS DOORS". PLEASE | | | PROVIDE CUT SHEETS FOR PLANNED LOCKS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|