| 2002-04-16 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 02031486 |
| | 200 FLAGLER LANE |
| | CONT: FRANK HADERCONST |
| | TEL: (561)735-3114 |
| | |
| | FL BLDG CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1)- FL BLDG CODE 1606.1.7 INFORMATION ON |
| | DRAWINGS RELATED TO WIND IS MISSING, SEE |
| | CODE SECTION, NEW! |
| | 2)- EXTERIOR WINDOWS & DOORS SHALL BE |
| | TESTEDD FOR WIND, TEST REPORTS SHALL |
| | INDICATE THE TEST PRESSURE & DESIGN |
| | PRESSURE. SBCCI OR DADE COUNTY REPORTS |
| | ARE ACCEPTED.FL BLDG CODE 1707.4.1. |
| | SEE NEW CODE SECTIONS 1707.4.2/1704.2.2 |
| | 3)- EXTERIOR DOOR ASSEMBLIES: SBCCI OR |
| | DADE COUNTY PRODUCT APPROVAL FOR EACH |
| | TYPE OF DOOR CONFIGURATION. |
| | 4)- 1707.4.5 MULLIONS BETWEEN INDIVIDUAL |
| | WINDOWS AND DOOR ASSEMBLIES. |
| | 5)- 1707.5 ROOF TILE PRODUCT TESTING |
| | REPORT, SBCCI OR DADE COUNTY REPORT. |
| | 6)- FL BLDG CODE 1606.1.4 PROTECTION OF |
| | OPENINGS, GLAZED OPENINGS TO HAVE LARGE |
| | MISSLE IMPACT TESTING OR STORM SHUTTERS |
| | 7)- FLORIDA ENERGY FORMS, OWNER OR AGENT |
| | TO SIGN FORMS. |
| | 8)- FLOOD ZONE A-5: CITY BASE ELEVATION |
| | HABITABLE AREAS 7'-6", A ELEVATION |
| | CERTIFICATE SHALL BE REQUIRED BY THE |
| | SURVEYOR AFTER MONOLITHIC SLAB IS POURED |
| | NOTE: POOL EQUIPMENT, A/C COMPRESSOR |
| | PADS SHALL BE SET AT A MINIMUM OF 7'-6". |
| | 9)- FL BLDG CODE 1707.3.1 TRUSS ANCHORS, |
| | MISSING INFORMATION ON TRUSS LAYOUT |
| | PLAN, TRUSS GIRDER LOADS, VERTICAL, |
| | HORIZONTAL & GRAVITY LOADS AND THE TYPE |
| | OF ANCHOR THAT SHALL BE USED TO RESIST |
| | THESE LOADS. |
| | 10)- FL BLDG CODE 424.17.1.9. POOL |
| | BARRIERS, WHERE A WALL OF A DWELLING |
| | SERVES AS PART OF THE BARRIER, ONE OF |
| | THE FOLLOWING SHALL APPLY: SEE CODE! |
| | 11) CONTRACTOR TO SUBMIT THE PLANS TO |
| | THE P. B. COUNTY BUILDING DEPARTMENT |
| | FOR IMPACT FEE ASSESSMENT. |
| | 12)- CONT TO PAY ADDITIONAL FEES, FOR |
| | RADON. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096X8412 |
| | ******PRIVACY WALL NOT PART OF BLDG |
| | PERMIT, A SEPERATE PERMIT IS REQUIRED*** |