2002-03-28 00:00:00*************** PROVISO ****************
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 AND RESUBMIT FOR REVIEW.
  
  
 1} PROVIDE A CALCULATION FOR THE
 ADDITIONAL LOAD BEING ADDED TO THE
 SERVICE PER 220-31.
  
 2} PLEASE SHOW THE PATH OF THE REROUTED
 CONDUIT TO THE POOL EQUIPMENT,AND THE
 SIZE AND NUMBER OF THE CONDUCTOR IT
 CONTAINS.
  
 3} INDICATE HOW THE NEW BUILDING IS
 BEING FED.
  