| Plan Review Notes For Permit 02031481 |
| Permit Number |
02031481 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-05-07 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE AFTER REVIEW OF | | | PLANS, NOTE #3 FROM FIRST REVIEW HAS | | | NOT BEEN ADDRESSED AND LOAD ON SOME | | | CIRCUITS DO NOT CORRELATE WITH THE | | | AMOUNTS SHOWN ON PLANS. | | | | | | 2)NOTE: PLEASE ALSO NOTE THAT THERE | | | ARE MANY CIRCUIT #`S ON PLANS THAT DO | | | NOT CORRELATE WITH PANEL SCHEDULES | | | SUBMITTED. PLEASE NOTE SOME LOADING OF | | | CIRCUTIS ALSO DO NOT CORRELATE WITH THE | | | AMOUNT OF RECEPTS ETC ON CIRCUITS? AND | | | PANEL SCHEDULES? | | | | | | PLEASE SEE NOTE (3) FROM FIRST REVIEW | | | AND SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|