Plan Review Notes
Plan Review Notes For Permit 02031481
Permit Number 02031481
Review Stop P
Sequence Number 1
Notes
Date Text
2002-04-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING/CHAPTER 11
  
 1) PLEASE INDICATE USAGE FOR TENANT
 SPACE TO PROPERLY CALCULATE MINIMUM FAC-
 ILITIES.
 2) PROVIDE CALCULATIONS FOR MINIMUM FAC-
 ILITIES.
 3) SHT A-1 DRINKING FOUNTAIN, SECTION
 4.1.3(10) PLEASE SHOW COMPLIANCE FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 4) SHT M-1 PLUMBING PLAN AND SANT RISER
 DIAGRAM, FLOOR DRAIN NOT APPROVED FOR
 INDIRECT WASTE FOR WATER HEATER T/P.
 FLOOR SINK REQUIRED FOR ALL INDIRECT
 WASTE, AND TRAP PRIMER REQUIRED TO PRO-
 TECT SEAL OF TRAP. SECTION 802.3
 5) IN MOST OCCUPANCIES A SERVICE SINK IS
 REQUIRED UNDER THE FBC-2001 MINIMUM FAC-
 ILITIES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377