Plan Review Notes
Plan Review Notes For Permit 02031481
Permit Number 02031481
Review Stop M
Sequence Number 1
Notes
Date Text
2002-04-10 00:00:002001 FLORIDA BUILDING CODE, MECHANICAL
  
 1.PLEASE PROVIDE MANUFACTURER
 INFORMATION FOR THE NEW AHU.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC, MECH TABLE 403.3 OR
 ASHRAE 62-89.
  
 3.SHOW COMPLIANCE WITH 2001 FBC, MECH
 601.4, PRESSURE DIFFERENTIALS ACROSS
 CLOSED DOORS WHERE RETURNS ARE
 CENTRALLY LOCATED SHALL BE LIMITED
 TO .001 INCH WC OR LESS.PROVIDE
 AIR DUCT PATHWAY OR AIR TRANSFER
 PATHWAYS FROM THE HIGH PRESSURE ZONE
 TO THE LOW ZONE.
  
 4.CONDENSATE SHALL DISCHARGE A MINIMUM
 OF 12 INCHES AWAT FROM THE BUILDING
 STRUCTURE AS PER 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.