| Plan Review Notes For Permit 02031481 |
| Permit Number |
02031481 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-10 00:00:00 | 2001 FLORIDA BUILDING CODE, MECHANICAL | | | | | | 1.PLEASE PROVIDE MANUFACTURER | | | INFORMATION FOR THE NEW AHU. | | | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER 2001 FBC, MECH TABLE 403.3 OR | | | ASHRAE 62-89. | | | | | | 3.SHOW COMPLIANCE WITH 2001 FBC, MECH | | | 601.4, PRESSURE DIFFERENTIALS ACROSS | | | CLOSED DOORS WHERE RETURNS ARE | | | CENTRALLY LOCATED SHALL BE LIMITED | | | TO .001 INCH WC OR LESS.PROVIDE | | | AIR DUCT PATHWAY OR AIR TRANSFER | | | PATHWAYS FROM THE HIGH PRESSURE ZONE | | | TO THE LOW ZONE. | | | | | | 4.CONDENSATE SHALL DISCHARGE A MINIMUM | | | OF 12 INCHES AWAT FROM THE BUILDING | | | STRUCTURE AS PER 2001 FBC 1503.4.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|