| Plan Review Notes For Permit 02031481 |
| Permit Number |
02031481 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-03 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE CLARIFY IF MAIN DISC`S | | | SHOWN ARE NEW OR ALSO EXSITING? IF NEW | | | PLEASE SUBMIT AIC RATING FOR MAINS.110-9 | | | | | | 2)NOTE: PLEASE CLARIFY HOW PANELS "B" | | | AND "D" ARE FED?? ARE FROM FEED THRU | | | LUGS FROM PANELS A, C? OR ARE THEY FED | | | FROM OCP IN PANELS "A AND "C"?? | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PLANS ARE SHOWING NEW LOADS, AND | | | EVERYTHING IS SHOWN AS CONNECTED LOAD. | | | 220-3,220-10,220-11,220-13. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION/ | | | CLARIFICATION FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|