2002-04-03 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE CLARIFY IF MAIN DISC`S
 SHOWN ARE NEW OR ALSO EXSITING? IF NEW
 PLEASE SUBMIT AIC RATING FOR MAINS.110-9
  
 2)NOTE: PLEASE CLARIFY HOW PANELS "B"
 AND "D" ARE FED?? ARE FROM FEED THRU
 LUGS FROM PANELS A, C? OR ARE THEY FED
 FROM OCP IN PANELS "A AND "C"??
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLANS ARE SHOWING NEW LOADS, AND
 EVERYTHING IS SHOWN AS CONNECTED LOAD.
 220-3,220-10,220-11,220-13.
  
 PLEASE SUBMIT THE ABOVE INFORMATION/
 CLARIFICATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  