Plan Review Notes
Plan Review Notes For Permit 02031473
Permit Number 02031473
Review Stop B
Sequence Number 1
Notes
Date Text
2002-04-19 00:00:00CHECKLIST:
 1-AFTER CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS, PLEASE TAKE DRAWINGS TO PALM
 BEACH COUNTY TO PAY IMPACT FEES. BRING
 BACK STAMPED DRAWINGS & PAID RECEIPT.
 2-ENGINEER TO PROVIDE ALL INFORMATION AS
 REQUIRED BY CHAPTER 471 OF FL. STATUTE
 WHEN SUBMITTING INFORMATION FOR PUBLIC
 RECORDS.
 3-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS. SEC. 2405.2 FBC 2001.
 4-DRAWINGS TO HAVE ALL INFORMATION AS
 REQUESTED ON SEC. 1606.1.7 FBC 2001.
 5-REVISE/UPDATE STRUCTURAL DOOR & WINDOW
 BUCK DETAILS & SPECS TO COMPLY WITH
 SEC. 1707.4.4.2 FBC 2001.
 6-CLARIFY COLUMN TYPE AT PATIO.
 FOUNDATION PLAN DOESN'T MATCH EXTERIOR
 ELEVATIONS AND PORCH SECTION. SEE
 COMMENTS ON PLANS.
 7-PROVIDE COMPLETE FRAMING DETAILS FOR
 DOOR & WINDOWS @ FAMILY RM. SPECIFY
 ALL FASTENERS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 8-PROVIDE ENERGY CALCULATIONS. NOTE:
 OWNER/AGENT TO SIGN AND DATE AT BOTTOM
 OF FORM.
 9-PROVIDE ATTIC ACCESS. SECTION 2309.6
 FBC 2001.
 10-UNABLE TO FIND CONNECTOR ETA ON USP
 2001 CATALOGUE. WHERE WAS IT TAKEN
 FROM? REVISE AS REQUIRED.
 11-SPECIFY EXTERIOR GYPSUM BOARD THAT
 COMPLIES WITH SEC. 703.5.7 FBC 2001.
 SEE ASTM C931. SPECIFY ALL FASTENERS.
 12-ROOF FRAMING PLAN: IT LOOKS LIKE
 THERE MAY BE A PROBLEM WITH WATER AT
 EXISTING FLAT ROOF WHERE NEW GABLE END
 WALL WILL BE ERECTED. SHOW DIRECTION
 OF SLOPE AT EXISTING ROOF AND SOLUTION
 IF RUNNING AGAINST NEW WALL.
 -SPECIFY ROOF SLOPE OF NEW FLAT ROOF.
 -PROVIDE DETAILS AND SPECS FOR METAL
 FLASHING AT INTERSECTION OF FLAT ROOF
 WITH GABLE END WALL.
 13-REVISE GABLE END WALL DETAIL TO
 COMPLY WITH SEC. 2117 FBC 2001.
 **ALSO, PROVIDE A COMPLETE WALL SECTION
 DETAIL FOR CONSTRUCTION OF NEW NORTH
 GABLE END WALL ABOVE EXISTING WALL.
 NOTE: SEE SEC. 2117 FBC REQUIREMENTS.
 14-PROVIDE PRODUCT APPROVALS FOR:
 A)GLASS BLOCK. SUBMITTED ONE IS EXPIRED.
 B)SWING DOOR. SUBMITTED ONE IS EXPIRED.
 **NOTES: LETTER THAT RENOVATES PRODUCT
 APPROVAL IS NOT GOOD. PRODUCT APPROVAL
 IS FOR "OUTSWING" DOOR. RENEWAL LETTER
 IS FOR "INSWING" DOOR & IS A DIFFERENT
 PRODUCT APPROVAL NUMBER.
 15-SEE PLANS FOR ADDITIONAL COMMENTS AND
 BRING BACK REVIEWED SET AFTER ORIGINAL
 DRAWINGS ARE REVISED TO EXPEDITE THE
 REVIEW PROCESS.
 16-VALUE DECLARED ON APPLICATION WAS
 UPDATED TO $28,371. THEREFORE, OWES
 $276.03 FOR UPDATED VALUE AND RADON
 FEES.